Triggering a Task From the Program: the EVENT Instruction and the Trigger That Gets Dropped

The EVENT instruction with its Task operand, next to the event task properties showing type Event, trigger EVENT Instruction Only, priority 1 and watchdog 500 ms

The Monitor tab on a 1756-L83E’s Shut_Down task reads Task Overlap Count 63. The task has executed 12 times since the last download, and three programs between them asked for it 75 times. Nothing faulted, nothing latched, and the numbers add up exactly: 12 plus 63 is 75. That is the whole of the EVENT … Read more

GSV and SSV on a ControlLogix: Reading the Controller’s Own Data, Including the Clock

Panel of a GSV against the WallClockTime object: class name WallClockTime, instance name left blank, attribute LocalDateTime, destination Clock[0], followed by the seven array elements filled in as year 2026, month 11, day 16, hour 17, minute 3, second 0 and microsecond 418250

GSV and SSV on a ControlLogix: Reading the Controller’s Own Data, Including the Clock About one alarm row in forty carried a timestamp that could not have happened: 17:03:00 with 941 250 microseconds, logged after a row reading 17:03:01 with 12 microseconds. Two programs were each doing their own GSV against the WallClockTime object, in … Read more

Axis Faults on a Logix Motion Axis: What AxisFault, MotionFault and the Attributes Are Telling You

A panel listing the nine defined bits of the AxisFault attribute on a Logix motion axis: PhysicalAxisFault, ModuleFault, ConfigurationFault, GroupFault, MotionFault, GuardFault, InitializationFault, APRFault and SafetyFault, each with what sets it and where to look next

Axis Faults on a Logix Motion Axis: What AxisFault, MotionFault and the Attributes Are Telling You On a 1756-L83E, Axis_01.AxisFault reads 1, Axis_01.MotionFault reads 0, and the 2198-D032-ERS3 in the panel is showing FLT S54 – POSN ERROR. Somebody will now spend twenty minutes looking for a motion fault that does not exist, because the … Read more

Catching a PLC Intermittent Fault with a Trend in the Controller: the Tags, the Rate, and the Latch That Keeps the Data

Eight tags in the PLC intermittent fault trend with where each comes from, how often it can change, and why it is in

Line 2’s palletiser infeed stops about once a shift with Infeed_Jam latched, the alarm log says “Infeed jam” with a time, and the 1756-L83E, the PowerFlex 525 and the 1756-IB16 feeding the discharge photo-eye all check out every time somebody looks. Whatever happens takes a few tens of milliseconds and happens hours apart, and the … Read more

Timestamping PLC Data on a Raspberry Pi: Which Clock Wins and Why Your Trend Repeats an Hour

plc programming plc data timestamps raspberry pi clocks repeated hour 1 plc

At 02:30 on Sunday 25 October 2026 a logger in Berlin writes a row, and sixty minutes later it writes another row stamped 02:30, and the trend viewer draws the second hour on top of the first. Meanwhile the controller it reads from keeps its own idea of the time as a LINT of microseconds … Read more