When an Axis Will Not Enable: the Six Gates MSO Has to Pass Before Anything Moves

A ladder rung with Run_Request in series with a normally closed Axis_01.AxisFault and a normally closed MSO_1.EN driving an output, with an Enable_PB contact in a parallel branch around the first contact

When an Axis Will Not Enable: the Six Gates MSO Has to Pass Before Anything Moves The MSO rung goes true on a 2198-D032-ERS3 axis, MSO_1.EN sets, and then nothing happens: no .DN, no .ER, no error code to look up, and the machine sits there. Axis_01.AxisState reads 5. Five is Inhibited, and a start … Read more

Axis Faults on a Logix Motion Axis: What AxisFault, MotionFault and the Attributes Are Telling You

A panel listing the nine defined bits of the AxisFault attribute on a Logix motion axis: PhysicalAxisFault, ModuleFault, ConfigurationFault, GroupFault, MotionFault, GuardFault, InitializationFault, APRFault and SafetyFault, each with what sets it and where to look next

Axis Faults on a Logix Motion Axis: What AxisFault, MotionFault and the Attributes Are Telling You On a 1756-L83E, Axis_01.AxisFault reads 1, Axis_01.MotionFault reads 0, and the 2198-D032-ERS3 in the panel is showing FLT S54 – POSN ERROR. Somebody will now spend twenty minutes looking for a motion fault that does not exist, because the … Read more

Safe Torque Off on a Kinetix 5700: Wiring the STO Connector, and What It Does Not Do

The STO connector on a Kinetix 5700 inverter: a dual-channel safety device with contacts 13/14 and 23/24 feeding STO-2 and STO-4, the supply common landing on STO-3, and the 16 pins of the plug named with their signals

Safe Torque Off on a Kinetix 5700: Wiring the STO Connector, and What It Does Not Do One contact of the gate switch opens a few hundred milliseconds before the other, and a second later a 2198-D032-ERS4 posts GuardStopInputFault. The axis will not come back with a normal fault reset. Both safety inputs have to … Read more