Reading a Kinetix 5700 Fault at the Drive: the Display, the Fault Log and the Four Places to Look

The Kinetix 5700 home screen drawn as a field-and-value panel: the fault code FLT S45 and the text FDBK COMM FL on the first line, the drive IP address on the second, DC BUS voltage on the third, and the soft menu items Setup, A/B and Menu tied to the navigation buttons underneath

Reading a Kinetix 5700 Fault at the Drive: the Display, the Fault Log and the Four Places to Look The LCD on a 2198-D032-ERS3 reads FLT S45 – FDBK COMM FL, the MOD indicator above it is flashing red, and the line has been down for eleven minutes. Before anyone fetches a laptop, the drive … Read more

Registration and the MAR Instruction: Catching a Mark at Speed on a Kinetix 5700

IOD connector of a 2198-D032-ERS3 drawn as a ten-terminal strip with the registration sensor on pin 6, IN3, the sensor common on pin 7 and the cable screen landed on pin 10, alongside the Enable and Home inputs on pins 1 and 3

Registration and the MAR Instruction: Catching a Mark at Speed on a Kinetix 5700 A Kinetix 5700 inverter latches a registration event with ±3 µs accuracy and 700 ns repeatability, and its propagation delay is compensated to zero. At 1.5 m/s that accuracy figure is 4.5 µm of position uncertainty. The photoeye in front of … Read more

Soft Travel Limits, Hard Limits and the Overtravel That Faults a Kinetix Axis

IOD connector of a 2198-D032-ERS3 drawn as a ten-terminal strip: IN1 Enable on pin 1, common on 2, IN2 Home on 3, common on 4, shield on 5, IN3 Positive Overtravel on 6 wired through a normally closed plus limit, common on 7, IN4 Negative Overtravel on 8 through a normally closed minus limit, common on 9, shield on 10

Soft Travel Limits, Hard Limits and the Overtravel That Faults a Kinetix Axis A registration input on a Kinetix 5700 inverter gets a 12.0 µs pulse reject filter. The overtravel input, on the same IOD connector and the same silicon, gets the 20 ms nominal debounce that every other input function gets. At 500 mm/s … Read more

Scaling a Kinetix Axis in Real Units: Position Units, the Conversion Constant and the Gearbox

Four boxes left to right with the same displacement written under each: motor VPL-B1303C at 4000 counts per rev showing 16,000 feedback counts, a 4:1 gearbox showing 4 motor revs, a 5 mm lead ball screw showing 1 screw rev, and the load in millimetres showing 5.000 mm

Scaling a Kinetix Axis in Real Units: Position Units, the Conversion Constant and the Gearbox A new Kinetix axis is scaled one Position Unit per motor rev, at 1,000,000 Motion Counts per rev, and on Unlimited travel that axis rolls its position accumulator over after 2,147 revolutions. The motion runs through the rollover perfectly smoothly. … Read more

Tuning a Kinetix 5700 Axis: Load Ratio, Bandwidth and the Autotune That Lies

Step response of the same position loop at three bandwidths: 8.2 Hz settling inside two percent at 91 ms, 41.7 Hz at 22 ms, and 101.7 Hz peaking at 112.6 percent before settling at 9 ms, all against a target line at 100 percent

Tuning a Kinetix 5700 Axis: Load Ratio, Bandwidth and the Autotune That Lies Loop Response on the General page of a Kinetix axis is a three-item dropdown, and on a drive with the default 1.5 ms model time constant it moves the position loop between 8.2 Hz and 101.7 Hz. That is a factor of … Read more

Driving a Motor from a ControlLogix: From a Rung to a Turning Shaft on a Kinetix 5700

Five boxes left to right: Your task with MAM executing once in an 8 ms periodic task, Motion group with the planner and a 2.0 ms coarse update in the same controller, 1756-EN4TR carrying the motion connection at a 2.0 ms RPI, 2198-D032-ERS3 inverter axis 1 rated 32 A, and a VPL-B1303C motor at 2.0 Nm on a single Hiperface DSL cable

Driving a Motor from a ControlLogix: From a Rung to a Turning Shaft on a Kinetix 5700 A 2198-D032-ERS3 inverter, a VPL-B1303C motor on one Hiperface DSL cable, and a 1756-L83E that has never carried a motion group. Two rungs will turn that shaft — an MSO and then an MAM — and neither is … Read more

MAH and Homing a Kinetix Axis: The Switch, the Marker, and the Home That Lands in the Wrong Place

Position and velocity against time for a home to switch then marker: forward at 25 mm/s to the switch at 62 mm, reverse at 5 mm/s until the switch clears, on to the marker at 55.4 mm

MAH and Homing a Kinetix Axis: The Switch, the Marker, and the Home That Lands in the Wrong Place A home-to-switch-then-marker sequence at a Home Speed of 25 mm/s and a Home Return Speed of 5 mm/s takes just over four seconds on a 2198-D032-ERS4 axis, and 1.5 of those seconds are spent crawling back … Read more

MSO, MSF and MASD on a Logix Axis: Enabling It, Dropping It, and the One That Opens the OK Contact

Four boxes - Stopped, Running, Shutdown, Faulted - with MSO, MSF, MASD, MASR and MAFR on the arrows between them

MSO, MSF and MASD on a Logix Axis: Enabling It, Dropping It, and the One That Opens the OK Contact An MSO against a 2198-D032-ERS4 axis sets ServoActionStatus and DriveEnableStatus, and it does not set its own .DN bit in the scan that fired it. On a 2 ms coarse update period the drive answers … Read more

The Motion Group and the Coarse Update Period: What Happens When You Ask for Too Much

Three timelines of a 4.0 ms base update period with the motion task drawn as a coloured block at the start of each period and everything else in grey: eight axes leaving most of each period free, sixteen axes leaving little for the ladder, and twenty-four axes where the motion task fills the whole period and runs into itself, annotated with GroupFault.GroupTaskLoadingFault bit 2

The Motion Group and the Coarse Update Period: What Happens When You Ask for Too Much Bit 2 of MOTION_GROUP.GroupFault is GroupTaskLoadingFault, and the motion instruction reference describes it in plain words: the group coarse update period is too low, and user application tasks are not getting enough time to execute. That is a 1756-L84E … Read more