Triggering a Task From the Program: the EVENT Instruction and the Trigger That Gets Dropped

The EVENT instruction with its Task operand, next to the event task properties showing type Event, trigger EVENT Instruction Only, priority 1 and watchdog 500 ms

The Monitor tab on a 1756-L83E’s Shut_Down task reads Task Overlap Count 63. The task has executed 12 times since the last download, and three programs between them asked for it 75 times. Nothing faulted, nothing latched, and the numbers add up exactly: 12 plus 63 is 75. That is the whole of the EVENT … Read more