Time Sync Across a Cell: PTP on EtherNet/IP, NTP on PROFINET, and Why the Two Logs Disagree

A cell with a 1756-TIME GPS grandmaster feeding a Stratix 5400 in boundary mode on the EtherNet/IP side and an S7-1500 NTP client on the PROFINET side, showing what each half receives and what is deactivated by default

The guard door opens once and gets recorded twice: 06:41:12.310 in the Logix log, 06:41:12.650 in the S7-1500’s diagnostics buffer. The two controllers are eight metres apart on the same machine, both nominally synchronised, and the gap is a third of a second every time you look. Neither clock is broken. The Logix side is … Read more

Unicast or Multicast on an EtherNet/IP I/O Connection: the Checkbox and What It Decides

Two drawings of the same drop: on the left, unicast, where a 1756-EN2T owner at 192.168.1.10 receives one stream from a 1734-AENTR at 192.168.1.50 and a second controller at 192.168.1.11 receives nothing, its listen-only connection rejected with 16#0106; on the right, multicast, where the adapter sends one stream to a group address and the switch delivers it to both controllers, with the owner and the listen-only connection both marked multicast

Unicast or Multicast on an EtherNet/IP I/O Connection: the Checkbox and What It Decides Module fault 16#0106 appeared on the second controller’s listen-only copy of a 1734-AENTR drop, and the string underneath it reads “Module owned and configured by another controller. Module may accept only one connection if Unicast is used.” The owning controller had … Read more