Connecting a Python OPC UA Client to an S7-1500: Certificates, Security Policy and the Anonymous Login That Fails

The CPU's OPC UA server settings drawn as field and value: server on, port 4840, None off, Basic256Sha256 Sign and Encrypt on, trusted clients pi1-logger.der, automatic accept off, guest off, user logger, runtime licence

BadIdentityTokenRejected is the answer an OPC UA server gives when the secure channel is up, the client certificate is trusted, and the session request arrives with no user in it, and on an S7-1500 with guest authentication off that is exactly where a first Python OPC UA client stops. It is the third of four … Read more

Powering a Raspberry Pi from Panel 24 VDC: The 1606 Supply, the Ride-Through and the Shutdown Signal

The DIN rail left to right: the 1606-XLE240E with DC-OK on 13/14, the 1606-XLSBUFFER24 on the same bus, a 2 A branch fuse, the 24 V to 5.1 V converter, and the Pi with GPIO17 fed from the contact

A 1606-XLE240E Series B has a DC-OK relay on terminals 13 and 14 that closes while the 24 V bus is above 90 % of its set point, and a Raspberry Pi 4 needs 5.1 V and somewhere between five and twenty seconds of notice to halt without corrupting its card. Raspberry Pi panel power … Read more

A Safety Reset That Is a Rising Edge, Not a Level: The One Rung That Stops an Automatic Restart

The reset station three ways: the blue momentary button wired from T2 to I4 as designed, the same button taped down, and a jumper or a held HMI bit across the contact

The guard on the case packer closed at 14:07 and the infeed conveyor started on its own, with the blue reset button 4 m away and nobody within reach of it. The DCS instruction on that gate was configured Restart Type Manual, exactly as the drawing said, and the machine still restarted, because the button … Read more

Reading a Logix Tag into Node-RED on a Raspberry Pi Without Writing Code

plc programming logix tag node red raspberry pi no code 1 plc

A Node-RED Logix tag read takes one install script, one palette install and two dialogs on a Raspberry Pi 4: Zone7_Speed from a 5069-L306ER appears in the debug sidebar as 30.0, and none of it involves typing a line of code. The node that does it is node-red-contrib-cip-ethernet-ip 1.1.3, installed from the palette manager, configured … Read more

Timestamping PLC Data on a Raspberry Pi: Which Clock Wins and Why Your Trend Repeats an Hour

plc programming plc data timestamps raspberry pi clocks repeated hour 1 plc

At 02:30 on Sunday 25 October 2026 a logger in Berlin writes a row, and sixty minutes later it writes another row stamped 02:30, and the trend viewer draws the second hour on top of the first. Meanwhile the controller it reads from keeps its own idea of the time as a LINT of microseconds … Read more

Modbus TCP from a Raspberry Pi: Register Offsets, and Why Your Value Is One Address Out

plc programming modbus tcp raspberry pi register offset 1 plc

read_holding_registers(40011, count=2) comes back with exception code 02, read_holding_registers(11, count=2) decodes to -2.4e-41, and the 230.5 V the meter shows on its own display is sitting at address 10. That is the Modbus TCP register offset, and it is the fault everybody hits on their first evening with pymodbus 3.15.0 and a power meter on … Read more

Photo-Eye Placement on an Accumulation Zone: Distance From the Discharge and What a Long Box Does

Three zones in side view with the eye 150 mm back from the discharge: a stopped 600 mm carton with 750 mm of zone behind it, and a stopped 1219 mm carton with 131 mm

A 42EF retroreflective eye bolted 150 mm back from the discharge roller of a 1.5 m zone stops a 600 mm carton with 750 mm of zone still behind it, and stops a 1219 mm carton with 131 mm. Move the same eye to 50 mm from the discharge and the first carton overshoots into … Read more