Wiring a Pt100 into an Analogue Input and Getting Degrees Out: Three-Wire Compensation and the Open-Circuit Reading

The Pt100 head with its three leads, the 22 m run, and the two terminal strips it lands on: IN-0/A, IN-0/B and RTN-0/C on the 1756-IR6I with the two-wire short drawn dashed, and M+, M-, I+ and I- on the SM 1231 RTD with the bridge the S7-1500 function manual describes

A Pt100 RTD input wired two-wire over 22 m of 0.5 mm² cable into channel 0 of a 1756-IR6I reads 104.1 °C in a bath that the reference thermometer says is 100.0 °C, and the same sensor with its third lead landed on RTN-0/C reads 100.0 °C. Lift lead A off the module and the … Read more

Speed Matching Two Conveyor Sections So Product Does Not Bunch at the Transfer

The transfer in side view: the takeaway at 0.500 m/s handing over the nose-over to the palletiser infeed at 0.462 m/s, a 1219 mm carton bridging the gap with its nose on the slow belt, the pitch closing from 1429 to 1320 mm, the 210 mm gap becoming 101, and PE_X 0.6 m past the transfer

Two PowerFlex 525s with 42.50 Hz on both keypads were running the takeaway at 0.500 m/s and the palletiser infeed it hands over to at 0.462 m/s, and every carton that crossed the transfer between them arrived 7.6% closer to the one in front than it had left. A 1219 mm carton that left the … Read more

Commanding a PowerFlex 525 from a ControlLogix: The Command Word, the Reference and the Status Bits

Bit 0 of the PowerFlex 525 logic command word is Normal Stop, and it has to be sitting at 0 before bit 1 will ever start the drive. That footnote under the table in Appendix D of 520COM-UM001 is behind most of the drives that show a green connection in the I/O tree and still … Read more