Moving an S7-315 Program onto an S7-1500: What the Migration Converts and What It Hands Back to You

The two-stage path from a STEP 7 V5.x project to an S7-1500 program, with the CPU 315-2 PN/DP rack and its addresses on one side and the CPU 1515-2 PN with no modules on the other

A CPU 315-2 PN/DP with 6ES7315-2EH14-0AB0 on the label maps to a CPU 1515-2 PN, 6ES7515-2AM01-0AB0, in the Siemens migration guide’s CPU table, and the S7-1500 migration does not happen in one move. It happens in two, the second of which is a right-click on the old CPU in the device view called Migrate to … Read more

Building a Two-Step Sequence in TIA Portal GRAPH: Transitions, Interlocks and the Step That Never Advances

The two-step sequencer in the sequence view: S1 Fill, T1, S2 Heat expanded to show its action table, interlock network, supervision network and transition T2, and the jump from T2 back to S1; below it the call from OB1 with the standard interface parameters

Step 2 of a two-step TIA Portal GRAPH sequencer on a CPU 1515-2 PN has been active for 4 minutes 12 seconds by its own S2.T, the transition below it has been satisfied for the last 40 of those seconds, and the sequencer is still sitting on step 2. The heater that step 2 drives … Read more

Catching an Intermittent Bit on an S7-1500 with a Trace: Trigger Condition, Sample Rate and Recording Length

plc programming s7 1500 trace intermittent bit trigger sample rate recording length 1 plc

Zone 3 of the takeaway conveyor stops about once a shift with “Zone3”.Fault latched, the photo-eye on %I4.3 reads a steady 1 in every watch table anybody has opened, and the CPU 1516-3 PN/DP is turning OB1 over in about 6 ms. Whatever is happening is happening inside one of those 6 ms passes, hours … Read more

Wiring a Pt100 into an Analogue Input and Getting Degrees Out: Three-Wire Compensation and the Open-Circuit Reading

The Pt100 head with its three leads, the 22 m run, and the two terminal strips it lands on: IN-0/A, IN-0/B and RTN-0/C on the 1756-IR6I with the two-wire short drawn dashed, and M+, M-, I+ and I- on the SM 1231 RTD with the bridge the S7-1500 function manual describes

A Pt100 RTD input wired two-wire over 22 m of 0.5 mm² cable into channel 0 of a 1756-IR6I reads 104.1 °C in a bath that the reference thermometer says is 100.0 °C, and the same sensor with its third lead landed on RTN-0/C reads 100.0 °C. Lift lead A off the module and the … Read more

Uploading a Program from an S7-1500 Nobody Documented: What Comes Back and What Is Gone

plc programming upload program undocumented s7 1500 what comes back 1 plc

A CPU 1516-3 PN/DP in RUN on the filler, a SIMATIC memory card behind its front flap, and no project file on any laptop in the building. An S7-1500 upload – online, Upload device as new station (hardware and software) – and about three minutes later an empty project holds the rack, every block with … Read more