Setting Up a PID in Studio 5000: PIDE Gains, Units and the First Bump Test
Read process gain, dead time and time constant off one bump test, then enter them in the units PIDE actually wants instead of the ones the PID wants.
Read process gain, dead time and time constant off one bump test, then enter them in the units PIDE actually wants instead of the ones the PID wants.
A 1756-IF8 analog input in integer mode lands on roughly -20,030 counts at 4 mA and 30,920 at 20 mA, which are not numbers anybody memorises. If the value in front of you is 3277, the card in the rack is a 1769-IF4 or 1769-IF8 running the Scaled-for-PID data format, and none of the 1756 … Read more
What is in a PLC rack and how the software sees it: power supply budget, CPU memory, I/O cards, tasks and routines, and tags against S7 addresses.
How to pick discrete and analog I/O, get sinking and sourcing right, set RPI and electronic keying, wire a 4-20 mA loop and scale the raw counts.
Wet well level control, pump alternation that shares the wear, chlorine dosing with long dead time, and remote sites over cellular Modbus that go quiet.