An Edge Gateway That Buffers: Six Hours Offline, and Then What

A table of three publishing strategies for the same machines over a six hour outage, showing the number of metric changes, the number of messages, the mean message size, the megabytes buffered and the resulting steady rate, with the no-deadband row highlighted at 31.66 megabytes

An Edge Gateway That Buffers: Six Hours Offline, and Then What Six hours of the carton transfer at its real change rates is 2.12 MB. Four machines on the same gateway is 8.49 MB. The same four machines with every tag published every second and no deadband on anything is 31.66 MB, and that is … Read more

The Feedback Fault That Is Not the Encoder: FLT S45, the DSL Cable and the Ground That Hides It

A terminal view of a DSL feedback connection on a Kinetix 5700: MF-A terminals D plus and D minus with a twisted pair on each, the cable braid landing in the shield clamp at the bottom front of the drive, and the motor power conductors and frame ground landing on the MP-A connector from the same jacket

The Feedback Fault That Is Not the Encoder: FLT S45, the DSL Cable and the Ground That Hides It A 2198-D020-ERS3 running a VPL-B1306F has thrown FLT S45 – FDBK COMM FL four times in six weeks, and there is a third motor on order. The drive has been measuring the actual cause the entire … Read more

Position Error and Following Error on a Kinetix Axis: What a Trend Says That FLT S54 Does Not

A trend of position error in millimetres across one MAM move on a 2198-D020-ERS3, rising on the acceleration ramp, flat during the slew, spiking to about 24 millimetres at 0.56 seconds, flat at 10.9 millimetres through the slew and returning to zero at rest, with the Position Error Tolerance drawn as a dashed line at 21.8 millimetres

Position Error and Following Error on a Kinetix Axis: What a Trend Says That FLT S54 Does Not A 2198-D020-ERS3 threw FLT S54 – POSN ERROR at 14:02 and again at 14:19, and the fault-code spreadsheet describes it in one sentence: the position error of the position control loop exceeded Position Error Tolerance for longer … Read more

Axis Faults on a Logix Motion Axis: What AxisFault, MotionFault and the Attributes Are Telling You

A panel listing the nine defined bits of the AxisFault attribute on a Logix motion axis: PhysicalAxisFault, ModuleFault, ConfigurationFault, GroupFault, MotionFault, GuardFault, InitializationFault, APRFault and SafetyFault, each with what sets it and where to look next

Axis Faults on a Logix Motion Axis: What AxisFault, MotionFault and the Attributes Are Telling You On a 1756-L83E, Axis_01.AxisFault reads 1, Axis_01.MotionFault reads 0, and the 2198-D032-ERS3 in the panel is showing FLT S54 – POSN ERROR. Somebody will now spend twenty minutes looking for a motion fault that does not exist, because the … Read more

Sparkplug B Properly: Birth and Death Certificates, Metrics and Rebirth

A five-stage chain showing CONNECT with clean start true and the NDEATH will at QoS 1, SUBSCRIBE to NCMD at QoS 1, NBIRTH at QoS 0 with sequence zero and every metric, DBIRTH at sequence one, and DDATA by alias, with three numbered break points marked underneath for a missing will, a missing subscription and a missing metric

Sparkplug B Properly: Birth and Death Certificates, Metrics and Rebirth The first message the carton transfer gateway sends is 592 bytes on the topic spBv1.0/Plant2_CartonLine/NBIRTH/GW-TR14, it carries all 19 metrics the node will ever publish, and it goes out at QoS 0 with the retain flag clear. Everything about that sentence looks wrong to somebody … Read more

Reading a Kinetix 5700 Fault at the Drive: the Display, the Fault Log and the Four Places to Look

The Kinetix 5700 home screen drawn as a field-and-value panel: the fault code FLT S45 and the text FDBK COMM FL on the first line, the drive IP address on the second, DC BUS voltage on the third, and the soft menu items Setup, A/B and Menu tied to the navigation buttons underneath

Reading a Kinetix 5700 Fault at the Drive: the Display, the Fault Log and the Four Places to Look The LCD on a 2198-D032-ERS3 reads FLT S45 – FDBK COMM FL, the MOD indicator above it is flashing red, and the line has been down for eleven minutes. Before anyone fetches a laptop, the drive … Read more

Registration and the MAR Instruction: Catching a Mark at Speed on a Kinetix 5700

IOD connector of a 2198-D032-ERS3 drawn as a ten-terminal strip with the registration sensor on pin 6, IN3, the sensor common on pin 7 and the cable screen landed on pin 10, alongside the Enable and Home inputs on pins 1 and 3

Registration and the MAR Instruction: Catching a Mark at Speed on a Kinetix 5700 A Kinetix 5700 inverter latches a registration event with ±3 µs accuracy and 700 ns repeatability, and its propagation delay is compensated to zero. At 1.5 m/s that accuracy figure is 4.5 µm of position uncertainty. The photoeye in front of … Read more

Soft Travel Limits, Hard Limits and the Overtravel That Faults a Kinetix Axis

IOD connector of a 2198-D032-ERS3 drawn as a ten-terminal strip: IN1 Enable on pin 1, common on 2, IN2 Home on 3, common on 4, shield on 5, IN3 Positive Overtravel on 6 wired through a normally closed plus limit, common on 7, IN4 Negative Overtravel on 8 through a normally closed minus limit, common on 9, shield on 10

Soft Travel Limits, Hard Limits and the Overtravel That Faults a Kinetix Axis A registration input on a Kinetix 5700 inverter gets a 12.0 µs pulse reject filter. The overtravel input, on the same IOD connector and the same silicon, gets the 20 ms nominal debounce that every other input function gets. At 500 mm/s … Read more

An MQTT Broker for Plant Data: Topics, QoS, Retained Messages and Last Will

The topic string plant2 slash pack slash carton1 slash tr14 slash belt1 slash amps drawn as six boxes labelled site, area, line, machine, device and signal, above a table of five subscriptions including the hash wildcard and the plus wildcard with what each one brings back and a warning on the bare hash

An MQTT Broker for Plant Data: Topics, QoS, Retained Messages and Last Will The topic string plant2/pack/carton1/tr14/belt1/amps is 42 bytes. The float it carries is four. Every publish of the motor current on one belt of the carton transfer therefore spends ten times as much on saying where the number came from as on the … Read more

Scaling a Kinetix Axis in Real Units: Position Units, the Conversion Constant and the Gearbox

Four boxes left to right with the same displacement written under each: motor VPL-B1303C at 4000 counts per rev showing 16,000 feedback counts, a 4:1 gearbox showing 4 motor revs, a 5 mm lead ball screw showing 1 screw rev, and the load in millimetres showing 5.000 mm

Scaling a Kinetix Axis in Real Units: Position Units, the Conversion Constant and the Gearbox A new Kinetix axis is scaled one Position Unit per motor rev, at 1,000,000 Motion Counts per rev, and on Unlimited travel that axis rolls its position accumulator over after 2,147 revolutions. The motion runs through the rollover perfectly smoothly. … Read more

Tuning a Kinetix 5700 Axis: Load Ratio, Bandwidth and the Autotune That Lies

Step response of the same position loop at three bandwidths: 8.2 Hz settling inside two percent at 91 ms, 41.7 Hz at 22 ms, and 101.7 Hz peaking at 112.6 percent before settling at 9 ms, all against a target line at 100 percent

Tuning a Kinetix 5700 Axis: Load Ratio, Bandwidth and the Autotune That Lies Loop Response on the General page of a Kinetix axis is a three-item dropdown, and on a drive with the default 1.5 ms model time constant it moves the position loop between 8.2 Hz and 101.7 Hz. That is a factor of … Read more

Driving a Motor from a ControlLogix: From a Rung to a Turning Shaft on a Kinetix 5700

Five boxes left to right: Your task with MAM executing once in an 8 ms periodic task, Motion group with the planner and a 2.0 ms coarse update in the same controller, 1756-EN4TR carrying the motion connection at a 2.0 ms RPI, 2198-D032-ERS3 inverter axis 1 rated 32 A, and a VPL-B1303C motor at 2.0 Nm on a single Hiperface DSL cable

Driving a Motor from a ControlLogix: From a Rung to a Turning Shaft on a Kinetix 5700 A 2198-D032-ERS3 inverter, a VPL-B1303C motor on one Hiperface DSL cable, and a 1756-L83E that has never carried a motion group. Two rungs will turn that shaft — an MSO and then an MAM — and neither is … Read more