ALMD and ALMA: Putting the Alarm in the Controller Instead of the HMI

The ALMD and ALMA operands with real values, and the ALARM_DIGITAL and ALARM_ANALOG members that carry the answer

On a ControlLogix 5580, Tank_Level_Alarm.Status.3 is set. Every one of HHInAlarm, HInAlarm, LInAlarm and LLInAlarm reads 0, the transmitter has been sitting at 94.0 against a high-high limit of 90.0 for six minutes, and no alarm exists anywhere on the system. Nothing is faulted and the ALMA instruction is scanning. Status bit 3 is AlarmLimitsInv, … Read more