THRSe, TSAM and FSBM: The Four Sensors and the Sequence That Has to Hold

A conveyor in plan with a light curtain in the middle and four muting sensors, S1 and S2 before it and S3 and S4 after it, each labelled with its position in the forward and reverse sequences, and the four timer windows S1-S2, S2-LC, LC-S3 and S3-S4 drawn as spans between them, with the note that each timer is 5 to 180,000 ms or 0 to switch that check off, the Maximum Mute Time is 0 to 3600 s and the Maximum Override Time is 0 to 30 s with a hold-to-run device

THRSe, TSAM and FSBM: The Four Sensors and the Sequence That Has to Hold An FSBM instruction sitting at Fault Code 16#9121 has already told you where to look, and it is not a sensor alignment problem yet. The third digit of that code is the step number: the instruction was in step 2 of … Read more

DCS and the Dual-Channel Family: Discrepancy Time, and the Two Faults With No Timer Behind Them

A four-column table of the dual-channel instructions with what each is for, its discrepancy range and what it adds: DCS for a stop device at 5 to 3000 ms adding Restart Type and Cold Start Type; DCST the same plus a forced test; DCSTL the same plus a lock request and lock feedback; DCSTM the same plus muting; DCM for monitoring a cam or limit switch at 0 to 3000 ms, adding an Equivalent-Active Low input type and a zero that disables the check; DCSRT for a start device such as an enable pendant, with an Enable input and a window measured on the way in; and THRSe with a 100 to 3000 ms range that means something different again

DCS and the Dual-Channel Family: Discrepancy Time, and the Two Faults With No Timer Behind Them A DCS instruction reporting Fault Code 16#4002 has not had a discrepancy in the sense anybody means by the word. That code means Channel A went to the safe state and came back to the active state while Channel … Read more

ESTOP and Its Two Reset Inputs: What a Safety Reset Actually Requires

The ESTOP instruction drawn as a panel of operands and values: Reset Type Manual with the note that Automatic energises Output 1 after 50 ms, Channel A on IN0 and Channel B on IN1 both normally open with safe equal to zero, Circuit Reset on IN2 where a zero to one transition energises Output 1, Fault Reset on IN3 where a zero to one transition clears Inputs Inconsistent, an Inconsistent Time Period of 500 ms marked fixed with no operand for it, and the outputs Output 1, Cycle Inputs, Circuit Reset Held On, Inputs Inconsistent and Fault Present with what each one means

ESTOP and Its Two Reset Inputs: What a Safety Reset Actually Requires An ESTOP instruction on a GuardLogix 5580 sitting with Fault Present on and Inputs Inconsistent on will ignore the blue button on the panel for as long as that button is wired to the Circuit Reset operand. Circuit Reset energises Output 1, Fault … Read more

Writing Your First Safety Routine: Standard Tags, Safety Tags, and the Mapping Between Them

Three boxes across the top showing which way data crosses: Standard task on the left holding standard controller tags, standard program tags and the note that HMI and MSG write here; Safety tag mapping in the middle, reached from Logic then Map Safety Tags, one standard tag to one safety tag copied at task start; Safety task on the right holding safety controller tags and safety program tags written only by safety logic. A return path along the bottom is labelled that standard routines read controller-scoped safety tags directly with no mapping needed. Below, a panel listing the five rules that decide whether a mapping pair is legal and the five states in which mapping is refused outright

Writing Your First Safety Routine: Standard Tags, Safety Tags, and the Mapping Between Them Put a standard BOOL on a rung inside a safety routine and Studio 5000 will not accept it; the browse list does not even offer the tag. Try the obvious workaround next and the software refuses that too, because you cannot … Read more

The Safety Task on a GuardLogix: What Runs In It, What Cannot, and How to Pick the Period

Safety Task Properties drawn as a panel of fields and values: Task type Periodic fixed, Period 20 ms with the range 2 to 500 ms and the note that it cannot be edited online, Priority 1 recommended, Watchdog 20 ms with the range 2 to 500 ms and the requirement that it be less than or equal to the period, one safety task per controller that cannot be deleted, routine language Ladder Diagram only, and the resettable maximum observed scan time

The Safety Task on a GuardLogix: What Runs In It, What Cannot, and How to Pick the Period The Safety Task Properties dialog on a GuardLogix 5580 takes a period between 2 and 500 ms and a watchdog between 2 and 500 ms, and the safety reference manual is explicit that the watchdog has to … Read more