Then the search is on the wrong card. In the Go online dialog, open the PG/PC interface dropdown and pick the ASIX adapter, the one with the cable in ...
ACK_NEC is TRUE, default I think, nobody's changed it since we set the station up on V17. ACK_REQ is also TRUE right now, since the fault cleared. The...
Do you have the panel project, or the panel itself? An MP277 or similar has a tag list with names against the same addresses, which gives you most of ...
Someone tightening the HMI and taking OPC UA with it. Nice catch.
Set the time zone and the DST rule in the CPU properties, swapped RD_SYS_T for RD_LOC_T, removed the +1 hour, downloaded this morning from V17. PLC st...
Asked them. They're on V17 Update 6. So the update level matters as well as the version? Their screenshot only said V17.
Two things I'd check. Does the CPU have the OPC UA runtime licence, the SIMATIC OPC UA S7-1500 one? I've read it isn't enforced technically but I'm no...
Then that's your answer. The panel takes a transfer in two cases: it's sitting in the Start Center, or the runtime's running and remote transfer is en...
It keeps the time over a power off, so this isn't a reset. It's exactly one hour, and only since the clocks went forward. NTP is fine as well, the CPU...
V17 here as well. Is the server actually running on the CPU? Online & diagnostics, OPC UA, "Server status" should say running and the session coun...
Direct cable, Wi-Fi off, Update operating system ran through in about eight minutes. Panel rebooted to the Start Center showing image V17. Transferred...