It will fire. Nothing wrong with that on a filter.
Same ceiling on the Siemens side, in case anyone reads this later. The IEC TIME type is a 32 bit signed value in milliseconds, so TON tops out at T#24...
That was it. The offline database had lost its address assignments against the hardware, almost certainly from the Save As the colleague did, and HW C...
6ES7 315-2EH14 is a S7-315-2 PN/DP, so that one is a 300 series. Important part for you: a 300 does not open in TIA Portal without the STEP 7 V5.x opt...
Greyed out because you changed the structure, that one is expected. For an optimised DB you take a snapshot of the monitor values first, then load wit...
You're right, it is not a backup problem. A 1200 has no battery at all, the retentive area lives in non volatile memory on the CPU, and it holds throu...
Fair enough, I guess the name member answers my objection. I would still keep it as one array rather than six separate sets, the maintenance is much t...
On our side we would put all six stations in one DB as an array and let the report take them by index, station 1 is index 0 and so on. Far less to mai...
You're right, they don't match. The card on the rail is 6ES7 223-1BL32-0XB0, DI16 DQ16, and the project on the server has 6ES7 223 1BH32 in slot 3, th...
Moved it to the end and changed the position in the device view to match, then loaded. Fault follows the card, so it is not the clip and not that posi...
Already did that on Friday, and again this morning with everyone else out of the project. Copied the whole folder to C: on my own machine, opened it t...
Spare went in this afternoon, straight out of the panel builder's box. Same flashing ERROR, same slot 3 faulted, and I loaded the hardware again after...
Opening HW Config from the Manager, double click on Hardware. It never gets as far as drawing the rack. The number is only in the corner, the title ba...