A USB stick in the drawer. That's how half of these end.
Interlock in the PLC. Ours is a running bit on the load rung.
Normal, sadly. The HMI compiler doesn't check PLC addresses.
The counter is reset at 1000 in FC45, but the reset compare came after the array read in the same network. So for one scan each time round, the read u...
Added a reintegration pushbutton on the panel and a white lamp next to it. ACK_REI is set from the rising edge of the button in the safety program, AC...
There isn't one, changing the access type rebuilds the block. Snapshot the actual values into start values first, then download at the next stop. Or d...
CPU properties, Protection & Security, Connection mechanisms, "Permit access with PUT/GET communication from remote partner". On the S7-1200 from ...
Because an optimized DB has no absolute addresses at all. The CPU stores the variables where it likes and the panel can only reach them by symbol, so ...
On the WinCC side we ended up the same way, more or less. I think every site gets there eventually. The recipe view on the panel is only an editor, th...
Is the node still presenting the certificate you imported? Compare the thumbprint in the CPU's trusted list with the one the node is using now.
Installed the updates up to Update 6 overnight, and the project opens this morning without a word. So it came down to the update level and nothing el...
Nothing writes it, so I put a pulse on ACK_REI from a test network in the safety program and the channel came straight back, value 1, QBAD FALSE. Can ...
DB120 is an "Array[0..999] of Real", so 4000 bytes, and byte 4000 is one element past the end. FC45 reads it with an index that comes from an Int coun...
Are the old HMI tags addressed absolutely, like %DB1.DBW0?
In TIA, does DB5 show an Offset column?