There's your mismatch. 1BL32 is 24VDC transistor outputs, 1PL32 is relay outputs. Same face, same channel count, different module as far as the CPU is...
In STOP the outputs go to their substitute values, and for a PROFINET IO device the output data gets marked invalid. Green LEDs, no valid setpoint. I'...
About 60 registers per site, in three blocks because the maps aren't contiguous. One after the other, the driver just works through them as a list. So...
There is a writeup on this here:/p>
V17 here too and I've had exactly this after a rename. Post the top entry of the CPU diagnostics buffer. Mine read "IO device failure, cell2-io, Not r...
Re-entered the values from the customer's recipe sheet, took the operator an hour and I owe him a coffee for it. Then enabled Download without reiniti...
It does. TIA opens projects from its own version and update level or lower, never higher. A project saved on V17 Update 6 won't open on V17 Update 2, ...
V17 here, but it's the same job on either side. Two ways. Logix ships a compare tool with RSLogix 5000, in the Rockwell Software folder, RSLogix 5000...
There's your problem. An ET 200SP needs the server module on the end, the small grey thing that comes in the box with the IM, it closes the backplane ...
Every PID_Compact I ship has RunModeByStartup left at default. Noted.
StopRuntime system function on a button. Hide it behind a login.