RE: Replaced ET 200SP F-DI 8x24VDC HF, PROFIsafe address error, module stays passivated

Module's fine if the order number and the firmware line on the label match. Paste the exact buffer text when you can, not from memory, and confirm: Ba...

37 minutes ago
Reply
RE: Consumed tag error 16#0127 invalid connection size after editing a UDT

In the middle upstream, at the end downstream. I put line speed next to the other REALs on the upstream side for tidiness and forgot by the time I did...

1 hour ago
Reply
RE: 3000 tag Logix project with names like B3_7 and Pump2new, how to rename it sanely

Started offline. Exported the L5X, did area C4 in a text editor, imported it into a copy, and it compiles on V31. That part's fine. The HMI side is w...

3 hours ago
Reply
RE: Consumed tag error 16#0127 invalid connection size after editing a UDT

Edited the UDT downstream, member on the end, same name and type. Downloaded on the break. Still 0127. Both sides show the new member in the tag. What...

6 hours ago
Reply
RE: S7-1200 bit set at the end of OB1 is seen one cycle late at the top, trace shows the lag

V17, noted. Which order are the two calls in OB1, network 1 and network 2? Post the network list, I think I know before you answer.

7 hours ago
Reply
RE: 3000 tag Logix project with names like B3_7 and Pump2new, how to rename it sanely

One PanelView Plus 7, and a historian through Kepware, about 400 tags between them I think. No MSGs that I've found yet, but I haven't found everythin...

12 hours ago
Reply
RE: Consumed tag error 16#0127 invalid connection size after editing a UDT

Only upstream. The downstream project still has the old UDT. Both on 32.012. So the consumer is expecting the old size. I think that's what 0127 is, i...

12 hours ago