Meter on the terminals overnight on min max and the minimum came back 17.8V. Watched it sag this morning every time the dust extractor contactor pulls...
There it is. It isn't dead, it is sitting there holding the same address as the new one. Nothing polls the old block so it says almost nothing, but i...
Unmanaged switch on a filler. There's the real fault.
Port was forced, you were right about that much. 100 full on the switch, auto on the adapter. Set both ends to auto and left it an hour. Still doing ...
Filmed it and stepped through it frame by frame. It goes 1734-AENTR, then FW 4.011, then 192.168.2.31, then back to 1734-AENTR and round again. What ...
Which switch is it, make and model, and is it managed? And did the drive log anything at all in its fault queue, or is the queue empty?
Switch model first, and is the filler on its own switch or does it uplink to a core? When you say three or four times a shift, is it actually random,...
Get the querier line into their standard config while they're still listening. The next switch will have the same gap.
Went that way. Sequence is the CASE in ST, 30 steps in about 220 lines, step number and name on the HMI. Every valve and motor has its own ladder rung...
It lists the card because it's the sender, not a found device.
Steel handrail is my bet. Walk it round with the laptop and watch the RSSI.
The dock card is first in every list. Costs me ten minutes regularly.
Electrician read the coil on the discharge gate solenoid, 3 ohm. Bad coil. New solenoid this morning, 41 ohm. Then I toggled the FuseReset bit for th...
Overnight load duty was 31% the first night. Closed the paint zone valve, decay from 7.0 to 6.2 took twice as long, so that's the zone. Rented the ult...