Doesn't need a UDT. Pretty sure that's not it. 16#0004 on a data table read is usually the target saying it can't find that tag. Same firmware both en...
Logix does the same if you give two AOI calls one backing tag. Different dialog, same headache.
Copy that .xc somewhere that is not the old laptop.
Both calls, what does the box above the FB name say, the instance DB? Same name on both?
Which contactor drops when you hit that button? Any? Or does the E-stop only go into the PLC input and nowhere else? Look at the panel, not the progra...
Same v20 on both? And is the desktop file what's actually in the controller? Upload and check that first or you'll spend the night diffing the wrong t...
How big is the card and how full is it? And what's the model's maximum data points set to, Data Log Models, Setup tab. One a second on 14 tags fills a...
The spare's fine, it's empty. ControlNet has a keeper, one module on the network holds the schedule and the network parameters, and on a line that age...