Before you rip out whatever he added, find out why. A 3 second wait in front of a pusher usually has a reason, even an undocumented one.
Not a password, not a licence. Is the safety task locked, the padlock closed? And whoever put that line in left a commissioning report somewhere, they...
Then you don't have an E-stop, you have a stop button painted red. That was common on small shop machines in 2009, if I remember right it was cheap an...
Does anything monitor K5? Anything at all that checks it actually dropped when the button was pressed. And is it one contactor or two in series? In 19...
Doesn't need a UDT. Pretty sure that's not it. 16#0004 on a data table read is usually the target saying it can't find that tag. Same firmware both en...
Logix does the same if you give two AOI calls one backing tag. Different dialog, same headache.
Copy that .xc somewhere that is not the old laptop.
Both calls, what does the box above the FB name say, the instance DB? Same name on both?
Which contactor drops when you hit that button? Any? Or does the E-stop only go into the PLC input and nowhere else? Look at the panel, not the progra...
Same v20 on both? And is the desktop file what's actually in the controller? Upload and check that first or you'll spend the night diffing the wrong t...
How big is the card and how full is it? And what's the model's maximum data points set to, Data Log Models, Setup tab. One a second on 14 tags fills a...
The spare's fine, it's empty. ControlNet has a keeper, one module on the network holds the schedule and the network parameters, and on a line that age...