Shelf labels by description, not number. Found two wrong in our stores.
Wired the two NC mirrors in series into F-DI channel 5, FDBACK on the contactor output with a feedback time from the 3RT2 datasheet, new collective si...
Wire break diagnostics is a tick box per channel. Off by default.
Two shifts, nothing dropped, so I'm closing it. IGMP snooping with no querier on the VLAN, the switch pruned the multicast groups after the 260 s time...
Yes. Same as after any channel fault, press the reintegration button the OEM put on the panel, or whatever writes ACK_REI in that safety program. The ...
Added the feedback loop in SISTEMA with the DC from the table for direct monitoring. PL d, before touching a wire. Two spare F-DI channels on the stat...
Pick the one that matches how you started the instance. You started it on the virtual adapter, so choose "Siemens PLCSIM Virtual Ethernet Adapter" and...
That compile prompt catches me out too. No idea what it rebuilds.
IT enabled the querier on VLAN 30 with 10.30.0.2 this morning and rebooted the switch twice to prove it. 40 minutes, nothing dropped. In TIA world thi...
Loaded the four empty OBs last night. Panel dropped again at 06:10 this morning, buffer shows the station failure and the return, CPU stayed in RUN. L...
Two things it can be: the F-destination address, or a module firmware the HW config doesn't expect. The buffer says address, so it's the address. The...
DC for the output subsystem I set to none, because there is no feedback wired. The contactors just switch. The switch subsystem is at DC99 with the cr...
> is there an IGMP querier on that VLAN IT says "the router does that". The VLAN is layer 2 only, no SVI, nothing routes it. The show output says ...
Two things it can be, and yours is the first. In the project tree right click the project itself, Properties, Protection, and look for "Support simula...