Last seen: Sep 22, 2026
The light coloured BaseUnit starts a new potential group. Dark ones carry the supply along from the group before, a light one breaks it and takes its ...
Not faulty. That entry tells you the block and the byte offset, so it's a programming error, not hardware. What's in DB120 at byte 4000? An array, and...
Encoder output type, push-pull or open collector, and the pull-up value if it's open collector? And is that pulse width measured at the input terminal...
Online & diagnostics, Cycle time. What does it show for shortest, current and longest? Post the three numbers. And what's in the loop body, a UDT ...
DCP is Discovery and Configuration Protocol, the PROFINET service that lists devices and hands out names and IP addresses. It rides on plain Ethernet ...
RD_SYS_T gives you UTC. Always, on every 1500, and NTP feeds it UTC too, so that side is right. Your logic's fixed +1 was someone's way of getting loc...
Hardware support package. V18 shipped before V4.6 existed, so the catalog doesn't know about it. Siemens publishes an HSP for the new firmware and you...
What does the display say when you scroll to the overview, and is there a memory card in the slot on the front? Also the MAINT LED, on or off. And is ...
Expected. Rework those two for V2.2 and it runs, same CPU underneath.
Configured version can never be higher than what the CPU actually runs. Two paths. Right click the CPU in Devices & networks, Change device versi...