Reply
RE: PRONETA and TIA V17 find no PROFINET devices from the engineering VLAN, ping works

DCP is Discovery and Configuration Protocol, the PROFINET service that lists devices and hands out names and IP addresses. It rides on plain Ethernet ...

34 minutes ago
Reply
RE: S7-1500 time-of-day one hour off after DST, RD_SYS_T and the Comfort panel disagree

RD_SYS_T gives you UTC. Always, on every 1500, and NTP feeds it UTC too, so that side is right. Your logic's fixed +1 was someone's way of getting loc...

3 hours ago
Reply
RE: TIA V18 hardware catalog stops at V4.5, new S7-1200 CPU is firmware V4.6

Hardware support package. V18 shipped before V4.6 existed, so the catalog doesn't know about it. Siemens publishes an HSP for the new firmware and you...

4 hours ago
Reply
RE: S7-1500 swapped from stock stays in STOP, download finishes and nothing runs

What does the display say when you scroll to the overview, and is there a memory card in the slot on the front? Also the MAINT LED, on or off. And is ...

9 hours ago
Reply
RE: TIA V17 load to 1214C fails, CPU firmware lower than configured V4.4

Expected. Rework those two for V2.2 and it runs, same CPU underneath.

1 week ago
Reply
RE: TIA V17 load to 1214C fails, CPU firmware lower than configured V4.4

Configured version can never be higher than what the CPU actually runs. Two paths. Right click the CPU in Devices & networks, Change device versi...

1 week ago