RE: CIP Generic MSG to a PowerFlex 525 comes back 16#0005 every time

Class 0F and it read first try, 4.1 with the drive on the blower, same as the keypad says on b003. So it was never the path or the tag. I typed a dec...

2 weeks ago
Reply
3 weeks ago
Reply
RE: CIP Generic MSG to a PowerFlex 525 comes back 16#0005 every time

Typed it by hand, 2, 192.168.1.14, and put it back on the browsed one afterwards to be sure I hadn't broken anything. No change either way, still 0005...

3 weeks ago
Reply
RE: CIP Generic MSG to a PowerFlex 525 comes back 16#0005 every time

Studio 5000 v34. Drive firmware I'd have to go down and read off the keypad, I'll get it in the morning. Off the screen, Service Code e, Class 15, In...

3 weeks ago
Reply
RE: New FactoryTalk View ME app runs on the laptop, no live values on the PanelView Plus

Open the terminal's diagnostics list and read the first few lines, they usually say the quiet part out loud. Does any of it name your shortcut? If I ...

3 weeks ago
Reply
RE: PanelView Plus 7 setpoints snap back to 50 within a second of typing them in

Always a routine called Init_ something. Glad it wasn't the panel.

3 weeks ago
Reply
RE: 1756-EN2T at 100 percent CPU on its webpage, FactoryTalk View SE clients time out

Second EN2T went in Saturday, SE server, historian and Kepware all moved onto it. Slot 1 is at 22 percent CPU and 31 connections. Clients have been cl...

3 weeks ago
Reply
RE: PanelView Plus 6 refuses the MER from the machine builder, incompatible runtime version

Bigger is normal if they included the font files. Good result.

3 weeks ago
Reply
RE: 50 cartoner recipes, UDT array in the 1756-L73 or the HMI recipe manager?

Done over two nights. UDT Recipe, Recipes[60], Recipe_Active and Recipe_Edit, COP on load and save, index checked first. Indirect addressing gone off ...

3 weeks ago
Reply
RE: ControlLogix T04:C34 timer preset negative after operator loads a recipe

There it is, and it's not just one fix. Both sides need doing. Panel: Tags editor, Offset back to 0, then Minimum 100 and Maximum 5000 on the numeric ...

3 weeks ago
Reply
RE: PanelView Plus 7 jog button kept the Kinetix axis moving after the Ethernet was unplugged

A momentary button is two writes: 1 on press, 0 on release. The release write never arrived because the cable was out, and nothing in the PLC clears t...

3 weeks ago
Reply
RE: 1756-EN2T at 100 percent CPU on its webpage, FactoryTalk View SE clients time out

Cached the three MSGs, the other lines' programmers did it over lunch. Connections went from 118 down to 96. CPU's still 95 to 100. The SE clients sti...

3 weeks ago
Reply
RE: FactoryTalk View SE v12 client can't find the HMI server after a PC rebuild

One more thing. After the wizard, open Administration Console once and check the Network tree shows your area and the HMI server. If it does, the clie...

3 weeks ago
Reply
RE: Renamed the CompactLogix and every PanelView Plus screen went to tag error

You said you'd do the Runtime tab too. Did you? Test Application uses Design, the terminal uses Runtime. I think that's all it is. Copy from Design t...

3 weeks ago