RE: FactoryTalk View Studio v12 opens in demo mode after a server reboot

Started the service, launched V12, no banner, Create Runtime Application is back. Set the service to Automatic. So the activations were sitting there...

26 minutes ago
Reply
RE: 1769-IQ16 input chatters after wiring it in parallel with a 1734-IB8S safety input

Bumped the input filter on the IQ16 as far as it goes. No luck, just a slower flicker. Not sure which of your two makes more sense, is there a third p...

3 hours ago
Reply
RE: New PanelView Plus 7 shows //// in every numeric display, fine in Test Application

Communication Setup: is the shortcut on the Design tab or the Runtime tab?

3 hours ago
Reply
RE: GuardLogix DCS discrepancy fault on one E-stop about once a week, button tests fine

Pulled E-stop 3 tonight. From the front it looks fine. Behind it the holder is cracked on one side and block B rocks on its clip, block A is solid. Or...

3 hours ago
Reply
RE: Renamed the CompactLogix and every PanelView Plus screen went to tag error

Don't re-import anything. Communication Setup in the project. What does the PAL shortcut point at on the Design tab, and on the Runtime tab? Is it br...

4 hours ago
Reply
RE: Studio 5000 Watch window value never changes while the HMI shows it moving

Yes, on this L71. Without Program in the reference the PanelView reads the controller scoped tag, so that's the one the logic writes. The MainProgram ...

4 hours ago
Reply
RE: 3000 tag Logix project with names like B3_7 and Pump2new, how to rename it sanely

Area_Equipment_Signal, like C4_Conv_RunCmd. A UDT per equipment type, so a pump is one tag, C4_Pump2, with .Run, .Fault, .Amps as members, and the pum...

5 hours ago
Reply
RE: FactoryTalk View Studio v12 opens in demo mode after a server reboot

Stopped. Startup type is Manual. There's a second FactoryTalk service next to it that's Running and Automatic.

6 hours ago
Reply
RE: Can't open an RSLogix 5000 v20 project on a laptop with Studio 5000 v33 and v36

Yes. I think v20.05 is the release that runs on Windows 10 and 11, and 20.01 won't. Download RSLogix 5000 v20.05 from the Rockwell download center wit...

6 hours ago
Reply
RE: 1769-IQ16 input chatters after wiring it in parallel with a 1734-IB8S safety input

Pulse tested, yes. Test source T0. So the flicker is the module doing something on purpose?

8 hours ago
Reply
RE: FactoryTalk View Studio v12 opens in demo mode after a server reboot

activation manager 4.06 or thereabouts. Line shows Available, not In Use. View Studio just says demo mode, no error about not finding it.

12 hours ago
Reply
RE: Studio 5000 Watch window value never changes while the HMI shows it moving

In the Watch window, what does the Scope column say next to Jam_Count? And in the PanelView project, the tag on that numeric display, does the referen...

13 hours ago
Reply
RE: GuardLogix DCS discrepancy fault on one E-stop about once a week, button tests fine

Discrepancy time is 500, all five the same. Equivalent Active High. Random as far as anyone will admit, and always night shift, which is when forklif...

3 days ago