Nine days on the new holder and blocks, no DCS fault. It was the cracked holder letting channel B open late whenever something bumped the panel. Discr...
HMI tag or direct reference on that numeric entry?
The historian's 1,400 tags at 1 s. Kepware is 300 tags at 500ms, and IT say it's "just monitoring". No idea what cached means on a MSG, I do HMI. Each...
Operators on the panel, supervisor login. And yes, we added 3 setpoints two years ago and it took a day per recipe.
External Access None hides the tag from anything outside the controller, MSG, HMI, OPC. Fails like a missing tag, hence the 0004, as far as I know. fi...
Could be a version thing rather than a bad file. Two questions. What firmware is the terminal on, Terminal Settings, System Information? And what vers...
Design tab or runtime tab when you watched it? And is that a Numeric Input Enable or a Numeric Input Cursor Point? If FactoryTalk Security is on, whic...
Test Application uses the Design tab. The terminal uses the Runtime tab, and yours is empty, so every CP1 tag has nowhere to go and shows removed lin...
Went with the contact block for now, E-stop 2 had an empty position on the operator so I fitted an NC block and wired it to the IQ16 point and pulled ...
No. Design tab, open each display, Edit, Tag Substitution, old prefix to new prefix, one display at a time. That's why you lost half the screens, you ...
Started the service, launched V12, no banner, Create Runtime Application is back. Set the service to Automatic. So the activations were sitting there...
Bumped the input filter on the IQ16 as far as it goes. No luck, just a slower flicker. Not sure which of your two makes more sense, is there a third p...
Communication Setup: is the shortcut on the Design tab or the Runtime tab?