So the decel time does nothing at all once STO opens, I guess? We set 5 s on every conveyor and I always assumed the E-stop used it.
The firmware did nothing. It was the latch.
Grey patch lead, Cat5e, one of the ones out of the IT cupboard. Goes from the main panel across in the tray, into the drive panel through the bottom g...
Green means the connection is fine, the tree isn't it. The drive's running from the keypad because it's been told to. On the drive keypad read P046 an...
425 is well inside the range for a 400 volt drive, ours sit high too. So that's not your problem. Two questions before anything else. What's P042 set ...
F048 is Params Defaulted. It's the drive telling you it reset itself to factory after the flash, not a failed flash. What revision did you go from and...
RA from the old line says category 0 for the E-stops, and this is the same layout. Flat belt, light load, it coasts to a stop in a couple of seconds o...
Says Local Directory is selected. Screenshot attached. Not sure what that setting even means, I've never had to touch it, the other PCs were set up by...
Check them. Every one of ours was Exact Match until the day one wasn't.
Pulled all three. The C fuse body was discoloured on the clip end and the clip itself was brown, so new fuses went in and we changed the whole fuse bl...
Checked the timestamps against the compressor room. The 200hp backup compressor starts across the line within a few seconds of every one of them. It k...
What's the nameplate rpm on the motor? And is the drive in V/Hz or vector? Those two answer most of this.
Three class J fuses in a fused disconnect between the breaker and the drive. Locked out to get the cover off, then back on and measured at the line te...