Forum

vinnie86
@vinnie86
New Member
Joined: May 5, 2025
Last seen: Sep 19, 2026
Topics: 4 / Replies: 10
Reply
RE: PowerFlex 525 F004 undervoltage on several drives at the same second

Checked the timestamps against the compressor room. The 200hp backup compressor starts across the line within a few seconds of every one of them. It k...

26 minutes ago
Reply
RE: G120C says 1450 rpm, tacho says 1390, label pitch wrong

What's the nameplate rpm on the motor? And is the drive in V/Hz or vector? Those two answer most of this.

5 hours ago
Reply
RE: PowerFlex 755 input phase loss fault on a hot afternoon

Three class J fuses in a fused disconnect between the breaker and the drive. Locked out to get the cover off, then back on and measured at the line te...

6 hours ago
Reply
RE: Star-delta, soft starter or VFD for a 45 kW compressor

Fixed speed, no demand control, that's a soft starter job. It does what the star-delta was there for, limits the inrush, without the open-transition b...

7 hours ago
Reply
Reply
RE: PowerFlex 525 16#0116 electronic keying mismatch after drive swap

Pretty sure the spare's not bad. What firmware is on the old drive and what's on the new one? Keypad, scroll into the display group, the firmware vers...

15 hours ago
Reply
RE: FactoryTalk View SE v12 client can't find the HMI server after a PC rebuild

server is 12.00 with the same patch roll-up, I checked. IT turned the firewall off completely for the test, still no luck. Licence is a floating one o...

3 days ago
Reply
RE: Roof fan VFD trips overcurrent at start when the wind is up

Neither yet. Does it fault at 0 Hz the instant the start goes in, or does it get a second or two into the ramp? And is any DC braking set before start...

3 days ago
Reply
RE: Conveyor PowerFlex 525 won't restart after an e-stop until the run bit is toggled

Does that drive fault F059 when the e-stop hits, or just drop to Ready? And on the three that work, what's the run bit doing in the PLC during the e-s...

3 days ago
Reply
RE: 4-20 mA level signal noisy since a PowerFlex 755 went in

Could be the duct. A 755 puts a lot of edge on those leads. Where's the shield grounded, one end or both?

3 days ago