Upload the drive to CCW now and save it. Tonight.
The scope reading is the part nobody does. Good to have a number.
Ran a shielded industrial Cat5e in through the top gland on the other side of the panel, shield clamp at the panel entry, 8 in off the motor leads. Re...
Went with STO on the 5 hp PF525. Both relay outputs to S1 and S2 on their own wires, contactor dropped, disconnect on the door stays for lockout. Safe...
Write 6000. It's in hundredths of a hertz.
Then that's the story. Somebody got tired of the nuisance trips and set C143 to hold last so the drive would ride through the dropouts, instead of fin...
Recording meter on the MCC bus for a week, leads landed on the Sunday shutdown. Sags to about 390VAC for a good second on every backup compressor star...
Ran the wizard, picked Network Directory, entered the server name, logged in with the admin account, rebooted. Administration Console shows the applic...
Telegram 1 sends actual speed back in the second word. Scale it, show that.
Same as dan says. During the 3s decel the drive pulls the frequency down faster than that wheel can slow, so the wheel drives the motor, the motor tur...
The changeover bang killed that contactor. Years out of this one.
That's single phasing. C is open somewhere upstream and the 250 you see on it is the motor making it through its own windings. Two phases won't turn a...
C143, EN Comm Flt Action. It's what the drive does when the EtherNet/IP connection drops. Default is Fault, which is what your five did. The other opt...
The 4 seconds is the search. Normal for a big wheel.
We had this exact thing on a roof fan. Dropped the carrier to 2 kHz and the motor lasted longer, not forever. It still went eventually.