RE: Star-delta, soft starter or VFD for a 45 kW compressor

Fixed speed, no demand control, that's a soft starter job. It does what the star-delta was there for, limits the inrush, without the open-transition b...

3 weeks ago
Reply
Reply
RE: PowerFlex 525 16#0116 electronic keying mismatch after drive swap

Pretty sure the spare's not bad. What firmware is on the old drive and what's on the new one? Keypad, scroll into the display group, the firmware vers...

3 weeks ago
Reply
RE: FactoryTalk View SE v12 client can't find the HMI server after a PC rebuild

server is 12.00 with the same patch roll-up, I checked. IT turned the firewall off completely for the test, still no luck. Licence is a floating one o...

3 weeks ago
Reply
RE: Roof fan VFD trips overcurrent at start when the wind is up

Neither yet. Does it fault at 0 Hz the instant the start goes in, or does it get a second or two into the ramp? And is any DC braking set before start...

3 weeks ago
Reply
RE: Conveyor PowerFlex 525 won't restart after an e-stop until the run bit is toggled

Does that drive fault F059 when the e-stop hits, or just drop to Ready? And on the three that work, what's the run bit doing in the PLC during the e-s...

3 weeks ago
Reply
RE: 4-20 mA level signal noisy since a PowerFlex 755 went in

Could be the duct. A 755 puts a lot of edge on those leads. Where's the shield grounded, one end or both?

3 weeks ago