RE: Daily production count from a CompactLogix 5069 into Excel, no SCADA on site

Format it as an integer in the flow before it writes. And put a header row in once. The manager will stop asking.

3 weeks ago
Reply
RE: Single channel E-stop through one relay on a 1998 bagger, what PL does that reach

Rewired it over the weekend. 440R dual channel relay, both NC blocks on the mushroom, monitored reset, relay outputs through two 100-S contactors in s...

3 weeks ago
Reply
RE: SLC 5/04 limit switch on a vibrating frame runs the compact step twice

That's the off side. Add the TOF like I said, T4:21, same preset, use its DN.

3 weeks ago
Reply
RE: DeviceNet 1747-SDN, nodes at the far end of a 300 m trunk drop at 250 kbps

Carl was right. The spare at node 24 was still on 250, its DIP switches were under a label and I never lifted it. Set it, cycled it, and the whole net...

3 weeks ago
Reply
RE: Single channel E-stop through one relay on a 1998 bagger, what PL does that reach

Fresh assessment, she did it herself last month. So it's the whole thing. The mushroom already has a second NC block on it, never wired. Contactor is ...

3 weeks ago
Reply
RE: 1756-L61 lost its program after a power outage, BAT LED had been red

Nothing clever. New BA1 in the door with the chassis powered up, and the March download stays put. Then two things. Put the battery on the HMI: GSV Fa...

3 weeks ago
Reply
RE: Daily production count from a CompactLogix 5069 into Excel, no SCADA on site

DDE through Linx, there's a name I haven't heard in a while. It was the way once. Trouble is what you found, Excel has to be open. Does that engineer...

3 weeks ago
Reply
RE: Single channel E-stop through one relay on a 1998 bagger, what PL does that reach

Nothing monitors K5. One contactor. If K5 welded, the first anyone would know is when somebody pressed the button and nothing happened.

3 weeks ago
Reply
RE: SLC 5/04 limit switch on a vibrating frame runs the compact step twice

TON in front of it. Rung: XIC I:3/5 into TON T4:20, time base 0.01, preset 3, so 30 ms. Then use T4:20/DN everywhere you used I:3/5 for the home signa...

3 weeks ago
Reply
RE: DeviceNet 1747-SDN, nodes at the far end of a 300 m trunk drop at 250 kbps

Set every node to 125, switches on the 1791Ds, the parameter on the PowerFlex 40 card, scanner rate in RSNetWorx. Power cycled everything. Now the sca...

3 weeks ago
Reply
RE: 1756-DNB error 78 on node 5 after replacing a DeviceNet valve manifold

Set the dials to 05, kill power to the manifold, bring it back. Node address is read at power up on most of them, not live. Nothing in RSNetWorx neede...

3 weeks ago
Reply
RE: 1756-L61 lost its program after a power outage, BAT LED had been red

BAT LED red for weeks and then a power loss. That's your whole answer, but tell me: is there a 1756-BA1 in the front door of that L61, and when was it...

3 weeks ago
Reply
RE: DeviceNet 1756-DNB error 91 bus-off a few hours after conduit rework

About 60 is what you want. 118 is one resistor. Been there.

3 weeks ago
Reply
RE: 1756-CNB replaced, RSNetWorx for ControlNet keeper mismatch, I/O will not schedule

Found the contractor's .xc on the old laptop in the office, Extruder_CNet_2012.xc. Opened it, went online from it, Edits Enabled, Save, Optimize and r...

3 weeks ago