Right, it was the foam, and the mounting was making it worse. We moved the bracket out to 900mm off the wall over open water and dropped a 100mm PVC s...
Metered it at the head while it was spiking. Same swing, 6mA up to about 13mA and back, so the sensor is genuinely sending that. Lid bond is good, 0.3...
It's on a bracket off the access cover, maybe 300mm in from the wall, face about 4m above the slab so roughly 2.6m of clear air at normal level. Photo...
Same reason we're at 500 on the mushroom heads.
Sink or source means you pick. Per group. Good call on the NPN ones.
Twelve years at the limit. Somebody built that run right.
Five tanks, one guy. Check his 4-20 loops too.
Two mornings clean now. It was water sitting in the junction box overnight, insulation down to nothing cold and back up once the motor had run the da...
Moved the NC block on the right station to the front position, NO behind it, wires landed the same as the left station. Online, both buttons now chang...
Set the eight 1734 racks to 20 ms, the three 1756 racks to 10 because the guarding goes through them, drives at 10. Did it offline last night and down...
Preconfigured means someone put the label on. Ours came the same way.
Fitted the clip-on suppressor modules on all ten sockets, diode type, band toward +24 on every one. New card in. The drive vendor's guy was in for so...
One down. Who owns the SCADA box, does it get time from the domain?
Changed it to the seal-in yesterday, Start OR Run, Stop and the current alarm in series, OTE on Run. Killed the panel power with the pump running, bro...