RE: 1756-CNB replaced, RSNetWorx for ControlNet keeper mismatch, I/O will not schedule

No. The schedule lived in the keeper, but what you need to rebuild it is in the .xc file from commissioning and in the controller. Go online in RSNetW...

3 days ago
Reply
RE: FactoryTalk View SE 13 alarm and event server dead after every server reboot

> the exact Diagnostics line "Tag Alarm and Event Server 'AE_Line1' is not loaded" with the client reconnect lines31 after it. Nothing about a fai...

3 days ago
Reply
RE: Point I/O modules past slot 8 fault intermittently, 1734-AENTR itself is fine

How many modules exactly, what's in slots 1 to 20 in order, and is there a 1734-EP24DC anywhere in the rack? What's the AENTR firmware? A 20 module PO...

4 days ago
Reply
RE: 1791ES-IB16 safety connection times out a few times a day since a new managed switch

Module Properties on that 1791ES, Safety tab, Advanced. Connection Reaction Time Limit, and under it the Timeout Multiplier and the Network Delay Mult...