Two shifts in and it's within about 20 either way instead of 300. It was never the prox at all. The one-shot dealt with the counting every scan half o...
Wednesday had two jams on the infeed. Tuesday had none.
Scan is 5 to 7ms and no, nothing in front of it, the input went straight into the counter. Put an ONS in yesterday and ran a shift with it. Down from ...
Been running since Monday. Two NICs the way suel said, panel side on 192.168.1.50 with the gateway blank, KEPServerEX reading three tags off the L24, ...
Win10, and no. Panel is 192.168.1.x and the office side is 10.44.x. IT handed me a second NIC out of a drawer and told me to sort it out myself, which...
Got the labels. 1769-L24ER-QBFC1B in the main panel, v32 on the front of Studio when I went online, and the wrapper one is a 2080-LC50-24QWB. No slot ...
Fair enough, I don't actually know. There's a red faceplate thing in the main panel with 1769 printed on one of the cards, and a smaller grey one over...
Running at 60 now, conveyor's at line speed. Both parameters were still sat where the drive left the factory, and copying the module in the tree neve...
Ordered a Cosy through the distributor. IT approved it once they saw it only talks outbound on 443 and the service has MFA and a session log. Set the ...
Copy from Design to Runtime, writing that on the laptop lid.
Found a 2022 project on the old maintenance laptop. Compared to the 2019 backup, one thing changed: a spare IB8S point was added as a sixth E-stop whe...
Factory lead in, EN2T to the switch. Reset the counters Tuesday morning. FCS 0 after an hour, 0 at end of shift, still 0 today. The switch port gi1/1 ...
Fitted an overload under the contactor, dial at 4.8, NC contact wired in series with the coil. Tested it with the trip button, contactor drops. Rewoun...