RE: Case packer count on a 1769-L33ER always runs over the tally, worse on jam days

Two shifts in and it's within about 20 either way instead of 300. It was never the prox at all. The one-shot dealt with the counting every scan half o...

2 weeks ago
Reply
2 weeks ago
Reply
RE: Case packer count on a 1769-L33ER always runs over the tally, worse on jam days

Scan is 5 to 7ms and no, nothing in front of it, the input went straight into the counter. Put an ONS in yesterday and ran a shift with it. Down from ...

2 weeks ago
Reply
RE: Daily part count out of the PLC into Excel every morning, no SCADA here

Been running since Monday. Two NICs the way suel said, panel side on 192.168.1.50 with the gateway blank, KEPServerEX reading three tags off the L24, ...

2 weeks ago
Reply
RE: Daily part count out of the PLC into Excel every morning, no SCADA here

Win10, and no. Panel is 192.168.1.x and the office side is 10.44.x. IT handed me a second NIC out of a drawer and told me to sort it out myself, which...

2 weeks ago
Reply
RE: Daily part count out of the PLC into Excel every morning, no SCADA here

Got the labels. 1769-L24ER-QBFC1B in the main panel, v32 on the front of Studio when I went online, and the wrapper one is a 2080-LC50-24QWB. No slot ...

2 weeks ago
Reply
RE: Daily part count out of the PLC into Excel every morning, no SCADA here

Fair enough, I don't actually know. There's a red faceplate thing in the main panel with 1769 printed on one of the cards, and a smaller grey one over...

2 weeks ago
Reply
RE: PowerFlex 525 ignores the PLC start command, runs from the keypad

Running at 60 now, conveyor's at line speed. Both parameters were still sat where the drive left the factory, and copying the module in the tree neve...

2 weeks ago
Reply
RE: Remote view of a PanelView Plus 7 line HMI from home, IT refuses any port forward

Ordered a Cosy through the distributor. IT approved it once they saw it only talks outbound on 443 and the service has MFA and a session log. Set the ...

2 weeks ago
Reply
RE: New PanelView Plus 7 shows //// in every numeric display, fine in Test Application

Copy from Design to Runtime, writing that on the laptop lid.

2 weeks ago
Reply
RE: GuardLogix safety signature, auditor wants it in the validation file, what is it actually

Found a 2022 project on the old maintenance laptop. Compared to the 2019 backup, one thing changed: a spare IB8S point was added as a sixth E-stop whe...

2 weeks ago
Reply
RE: 1756-EN2T webpage media counters, what do FCS errors mean when a rack shows 16#0204

Factory lead in, EN2T to the switch. Reset the counters Tuesday morning. FCS 0 after an hour, 0 at end of shift, still 0 today. The switch port gi1/1 ...

2 weeks ago
Reply
RE: Line-fed screw conveyor motor burned out, panel builder skipped the overload

Fitted an overload under the contactor, dial at 4.8, NC contact wired in series with the coil. Tested it with the trip button, contactor drops. Rewoun...

2 weeks ago