RE: 1756-EN2T webpage media counters, what do FCS errors mean when a rack shows 16#0204

hand crimps. every plant has one and its always in the worst spot.

3 weeks ago
Reply
RE: PanelView Plus 7 setpoints snap back to 50 within a second of typing them in

Put S:FS in front of all 12 rungs and downloaded at the shift change. Setpoints hold now and the operators are happy. For anyone searching this later...

3 weeks ago
Reply
RE: Kinetix 5700 axis fault excessive position error at the end of fast moves

Velocity Feedforward to 100 percent on Y, tolerance back to 5mm. Ran 3000 cycles overnight, no fault. Trend now peaks at 0.6mm on the same move, same ...

3 weeks ago
Reply
RE: ControlLogix T04:C34 timer preset negative after operator loads a recipe

Done both. Offset back to 0 on the panel tag, min and max on the entry, and the LIM in front of the MOV. Loaded the 250ml recipe twelve times this mor...

3 weeks ago
Reply
RE: MSR127RP won't reset after replacing a contactor, K1 K2 LEDs stay off

stores had a 100 c09d01 on a different shelf, mirror symbol on the label. fitted it 06:00, 413 and 414 on the nc, k1 and k2 leds came on first reset. ...

3 weeks ago
Reply
RE: PNOZ X3 safety relay drops out for a second every time the 30kW mixer drive starts

drawing shows two supplies. ps2 for safety. there is no ps2 in the panel, just an empty din rail spot with a label. fitted a 1606 xle120e on that spo...

3 weeks ago
Reply
RE: SLC 5/04 limit switch on a vibrating frame runs the compact step twice

tof t4:21 added, home signal is t4:21/dn now. new bolts in the bracket, holes drilled out and sleeved by days. 120 cycles over two nights, zero double...

3 weeks ago
Reply
RE: PanelView Plus 7 setpoints snap back to 50 within a second of typing them in

It's a routine called Init_Values, 12 rungs of MOV with no conditions on them at all. Source 50, dest Fill_SP_1. Fill_SP_2 is the rung under it. The o...

3 weeks ago
Reply
RE: ControlLogix T04:C34 timer preset negative after operator loads a recipe

HMI tag. Opened Tags in the panel project, Glue_Dwell_ms has Scale 1 and Offset 2400. The 500ml tag next to it has Offset 0. Engineer says he copied t...

3 weeks ago
Reply
RE: MSR127RP won't reset after replacing a contactor, K1 K2 LEDs stay off

so the relay wants to see that block closed before it resets, i think. the right block is a week out and i have a supervisor standing here asking when...

3 weeks ago
Reply
RE: PNOZ X3 safety relay drops out for a second every time the 30kW mixer drive starts

min max caught 17.3VDC on start, back to 24.1VDC in under a second. supply is a 1606 xle240e, 24VDC 10a. on it: plc io, the 755 control side, the safe...

3 weeks ago
Reply
RE: PanelView Plus 7 setpoints snap back to 50 within a second of typing them in

Runtime, on the panel itself. Numeric Input Enable. Default user, no security set up on that panel as far as I know. The other setpoints on the same s...

3 weeks ago
Reply
RE: SLC 5/04 limit switch on a vibrating frame runs the compact step twice

ton in, 30ms, t4:20/dn on the home rung. 60 cycles tonight and one double. the led shows the input dropping out for a blink while the ram is sitting a...

3 weeks ago
Reply
RE: ControlLogix T04:C34 timer preset negative after operator loads a recipe

31.011. Caught it in the watch window. Glue_Dwell_TON.PRE goes to -1600 the moment the recipe lands, then the fault. The other recipes put 800, 1000, ...

3 weeks ago
Reply
RE: Kinetix 5700 axis fault excessive position error at the end of fast moves

Trend attached. Error climbs with the speed, sits around 8 or 9mm through the fast part, then collapses to 0.2mm once it stops. Position Loop tab: Pos...

3 weeks ago