Glad it was only the path. Loading at 05:30 is dedication.
1783-NATR went in on Wednesday. Two rules, PLC to 10.40.3.10 and HMI to .11. SE points at the public address, historian too. Line 3 consumed tag repoi...
Deleted 6,400 tags, 400 left, 60 of those at 250 ms leased. PanelView's back to about 200 ms a button, scan time back to 4 ms, port at 600 packets a s...
Set the three 1734 racks to Unicast at the shift change, about 40 s of I/O drop per rack. The box on the old 1794-AENT was greyed out so that one stay...
You want a Held state, ISA-88 calls it that and PackML does too. When safety OK drops, don't touch Step. Copy it to Step_Held, set Step to a Held valu...
Added the Second output and the TON. Pulled the cable again. Jog stopped at 3.2 s. Better, but during the test the axis also stopped once with the cab...
Right. A TON needs its rung true for the whole preset, it isn't a start command, it's a hold command. Take the ONS out and put the photoeye straight i...
Bill's right. That checkbox is exactly what it says, the adapter dropping becomes a controller major fault instead of a faulted module in the tree. An...
P046 is Start Source 1 and P047 is Speed Reference 1, and neither of yours is pointed at the network. Both want the EtherNet/IP entry. The two lists a...
Moved everything into a 2 s group and put the 60 OEE tags in a 250 ms group. PanelView's better, about 800 ms a button now. Not the 200 ms it was. Pac...
> Ask them what they do for other multi-machine sites Asked them. Answer was "most customers use a NAT router" and nothing else, no part number. I...
Hold time is 0. Jog velocity is 200 mm removed link PVP7 on v12, coarse update 4 ms. So pretty sure it isn't the button being slow. Pulled the cable...
Switched to sensorless vector, motor ID ran about a minute, stationary. Tacho's on 1446 at 50Hz commanded. Labels land within 1 mm. So it was slip th...
Receive sits around 3 Mbps with nothing running, and the packets counter on the adapter is climbing at a couple of thousand a second. I never looked a...
What's the ONS doing in front of the timer? What changed when you added it, or was it there from the start?