RE: Renamed the CompactLogix and every PanelView Plus screen went to tag error

Glad it was only the path. Loading at 05:30 is dedication.

3 weeks ago
Reply
RE: Two OEM CompactLogix packers both on 192.168.1.x, second one can't join the network

1783-NATR went in on Wednesday. Two rules, PLC to 10.40.3.10 and HMI to .11. SE points at the public address, historian too. Line 3 consumed tag repoi...

3 weeks ago
Reply
RE: PanelView Plus 7 on the cartoner went slow the day Ignition was connected to the L33ER

Deleted 6,400 tags, 400 left, 60 of those at 250 ms leased. PanelView's back to about 200 ms a button, scan time back to 4 ms, port at 600 packets a s...

3 weeks ago
Reply
RE: 1756-EN2T racks fault 16#0203 hourly, HMI PC freezes ten seconds at a time

Set the three 1734 racks to Unicast at the shift change, about 40 s of I/O drop per rack. The box on the old 1794-AENT was greyed out so that one stay...

3 weeks ago
Reply
RE: S7-1500 mixer sequence restarts from step 1 after every E-stop reset, batch dumped

You want a Held state, ISA-88 calls it that and PackML does too. When safety OK drops, don't touch Step. Copy it to Step_Held, set Step to a Held valu...

3 weeks ago
Reply
RE: PanelView Plus 7 jog button kept the Kinetix axis moving after the Ethernet was unplugged

Added the Second output and the TON. Pulled the cable again. Jog stopped at 3.2 s. Better, but during the test the axis also stopped once with the cab...

3 weeks ago
Reply
RE: TON never reaches DN, accumulator climbs a few ms then resets to 0

Right. A TON needs its rung true for the whole preset, it isn't a start command, it's a hold command. Take the ONS out and put the photoeye straight i...

3 weeks ago
Reply
RE: CompactLogix faults T03:C16 every time the remote Point I/O rack loses power

Bill's right. That checkbox is exactly what it says, the adapter dropping becomes a controller major fault instead of a faulted module in the tree. An...

3 weeks ago
Reply
RE: PowerFlex 525 ignores the PLC start command, runs from the keypad

P046 is Start Source 1 and P047 is Speed Reference 1, and neither of yours is pointed at the network. Both want the EtherNet/IP entry. The two lists a...

3 weeks ago
Reply
RE: PanelView Plus 7 on the cartoner went slow the day Ignition was connected to the L33ER

Moved everything into a 2 s group and put the 60 OEE tags in a 250 ms group. PanelView's better, about 800 ms a button now. Not the 200 ms it was. Pac...

3 weeks ago
Reply
RE: Two OEM CompactLogix packers both on 192.168.1.x, second one can't join the network

> Ask them what they do for other multi-machine sites Asked them. Answer was "most customers use a NAT router" and nothing else, no part number. I...

3 weeks ago
Reply
RE: PanelView Plus 7 jog button kept the Kinetix axis moving after the Ethernet was unplugged

Hold time is 0. Jog velocity is 200 mm removed link PVP7 on v12, coarse update 4 ms. So pretty sure it isn't the button being slow. Pulled the cable...

3 weeks ago
Reply
RE: G120C says 1450 rpm, tacho says 1390, label pitch wrong

Switched to sensorless vector, motor ID ran about a minute, stationary. Tacho's on 1446 at 50Hz commanded. Labels land within 1 mm. So it was slip th...

3 weeks ago
Reply
RE: 1756-EN2T racks fault 16#0203 hourly, HMI PC freezes ten seconds at a time

Receive sits around 3 Mbps with nothing running, and the packets counter on the adapter is climbing at a couple of thousand a second. I never looked a...

3 weeks ago
Reply
RE: TON never reaches DN, accumulator climbs a few ms then resets to 0

What's the ONS doing in front of the timer? What changed when you added it, or was it there from the start?

3 weeks ago