RE: Renamed the CompactLogix and every PanelView Plus screen went to tag error

The greyed out bit is the answer. The shortcut was saved with the browsed path ending in the old controller name. After the rename that hop is stale, ...

32 minutes ago
Reply
RE: Logix press station with an OTL per state ends up pressing and ejecting at the same time

One DINT tag, Step. One rung per transition: EQU Step 20, the condition, MOV 30 Step. Outputs in their own rungs, EQU Step 30 drives the press valve a...

2 hours ago
Reply
RE: G120C says 1450 rpm, tacho says 1390, label pitch wrong

Nameplate says 1440 rpm at 50Hz, 4 pole. So the motor can't even do 1450 at full load? Drive's in V/f linear, the default we shipped the G120 with. No...

3 hours ago
Reply
RE: Logix press station with an OTL per state ends up pressing and ejecting at the same time

What changed since it last ran clean, a sensor swap, an edit, a faster cycle? And when both bits are on, which transition rung set the second one? Loo...

11 hours ago
Reply
RE: 3000 tag Logix project with names like B3_7 and Pump2new, how to rename it sanely

Renaming online is the trap and you found it. Before a convention, what else reads these tags? One HMI, or a historian, MSGs from other controllers, K...

15 hours ago
Reply
RE: Conveyor PowerFlex 525 won't restart after an e-stop until the run bit is toggled

There's your difference. After a fault or a safety open the 525 wants a stop and then a fresh start edge. A run bit that has been true the whole time ...

23 hours ago
Reply
RE: 5069-L306ER local I/O green in the tree but no input ever turns on

It's not optional. MOD power runs the controller and the backplane, that's why everything is green and talking. SA power is the 24V for the field side...

1 day ago
Reply
RE: PanelView Plus 7 on the cartoner went slow the day Ignition was connected to the L33ER

Gateway says 6,800 tags on that device and they all sit in one tag group set to 100 ms and I think he just browsed the whole controller and dragged th...

1 day ago
Reply
RE: FactoryTalk View ME datalog stopped after three weeks, trend ends on a date, no error

3 MB free explains all of it. The datalog doesn't warn when the path fills, it stops writing and the trend ends on the last sample. Live values keep g...

2 days ago