RE: Case packer count on a 1769-L33ER always runs over the tally, worse on jam days

Put the forward run bit in series ahead of the CTU so the one-shot only ever fires while the belt is going the right way. Ours takes the drive running...

2 weeks ago
Reply
RE: Downtime reasons and OEE on a CompactLogix, or let the historian work it out

All three machines are on it as of Friday. State DINT with the priority order, timers per state, and a 32 deep event buffer with a sequence number tha...

2 weeks ago
Reply
RE: Case packer count on a 1769-L33ER always runs over the tally, worse on jam days

What is your scan time, and is there anything at all in front of that CTU. A prox that stays made for 40ms on a 6ms scan gives you seven counts for on...

2 weeks ago
Reply
RE: Downtime reasons and OEE on a CompactLogix, or let the historian work it out

Built the state DINT on the first cartoner and it's better, I can see blocked and starved separating out properly now. The reason code is where it fa...

2 weeks ago
Reply
RE: Downtime reasons and OEE on a CompactLogix, or let the historian work it out

SQL behind FactoryTalk View SE, and the MES lot talk to it through a stored procedure someone wrote in 2019 that nobody will touch. They can't read t...

2 weeks ago
Reply
RE: Parts per minute goes to a huge number at power-up, divide by zero on an S7-1500

It won't stop on you. If I remember right the integer DIV sets ENO false and doesn't write OUT at all, so you keep whatever was in there before, which...

2 weeks ago
Reply
RE: Excel sheet off a CompactLogix stopped updating, RSLinx topic still shows good

Sorted. The copy on the share was saved with calculation set to Manual, and because that one gets opened first every morning it put the whole Excel in...

2 weeks ago
Reply
RE: Excel sheet off a CompactLogix stopped updating, RSLinx topic still shows good

Counters are moving and it says one client, so RSLinx is fine, its doing what it should. Calculation says Manual. I didn't set that. And there are tw...

2 weeks ago
Reply
RE: PowerFlex 525 ignores the PLC start command, runs from the keypad

Source 2 and 3 only matter if a digital input selects them. Leave them.

3 weeks ago
Reply
3 weeks ago
Reply
RE: PanelView Plus 7 jog button kept the Kinetix axis moving after the Ethernet was unplugged

Preset moved to 5 s, trended a full shift, no false trips, longest gap on the Second tag was 1.8 s. Cable pull stops the jog at about 5.2 s, and manua...

3 weeks ago