The greyed out bit is the answer. The shortcut was saved with the browsed path ending in the old controller name. After the rename that hop is stale, ...
One DINT tag, Step. One rung per transition: EQU Step 20, the condition, MOV 30 Step. Outputs in their own rungs, EQU Step 30 drives the press valve a...
Nameplate says 1440 rpm at 50Hz, 4 pole. So the motor can't even do 1450 at full load? Drive's in V/f linear, the default we shipped the G120 with. No...
What changed since it last ran clean, a sensor swap, an edit, a faster cycle? And when both bits are on, which transition rung set the second one? Loo...
Renaming online is the trap and you found it. Before a convention, what else reads these tags? One HMI, or a historian, MSGs from other controllers, K...
There's your difference. After a fault or a safety open the 525 wants a stop and then a fresh start edge. A run bit that has been true the whole time ...
It's not optional. MOD power runs the controller and the backplane, that's why everything is green and talking. SA power is the 24V for the field side...
Gateway says 6,800 tags on that device and they all sit in one tag group set to 100 ms and I think he just browsed the whole controller and dragged th...
3 MB free explains all of it. The datalog doesn't warn when the path fills, it stops writing and the trend ends on the last sample. Live values keep g...