RE: PanelView Plus 6 numeric input writes 12 or 0 when the operator types 12.5, INT tag

Display set to 1 place as well, loaded it this morning. Operator typed 12.5, saw 12.5, PLC has 125, and the first batch dosed right. It came down to ...

3 weeks ago
Reply
RE: Kinetix 5500 won't enable, MSO errors and the drive shows safe torque off

Jumpered the two STO inputs to 24V and common to common as the drawing in 2198-UM001 shows. Display went from STO to the normal status, axis went Read...

3 weeks ago
Reply
RE: 1769-L33ER faults type 4 code 20 when the recipe number from the HMI reaches 20

Range check in with the -1, and limits on the panel field. Recipe 20 loads now and 25 gives the RecipeFault bit and a message instead of faulting the ...

3 weeks ago
Reply
RE: PID_Compact drives the chiller valve wide open when the tank gets cold, S7-1200

Ticked InvertControl, ran pretuning overnight with the tank at temperature, and the loop holds 8.0 within a couple of tenths this morning. Valve close...

3 weeks ago
Reply
RE: PNP prox on an ET 200SP F-DI safety input, short-circuit to P fault from the first scan

Output Signal Switching Device, the pair of self testing outputs on a safety sensor or curtain. Reliable is not the question. The prox has no way to f...

3 weeks ago
Reply
RE: Two OEM CompactLogix packers both on 192.168.1.x, second one can't join the network

Same job on our two filling lines from one OEM. SCALANCE S615 on the Siemens side, the 1783-NATR Lou named on the Rockwell side. The machine keeps its...

3 weeks ago
Reply
RE: PanelView Plus 6 numeric input writes 12 or 0 when the operator types 12.5, INT tag

Changed the input to Fixed position, 1 place, new MER. Typing 12.5 writes 125 now and the dosing's right. The display next to it still shows 125 thoug...

3 weeks ago
Reply
3 weeks ago
Reply
RE: Kinetix 5500 won't enable, MSO errors and the drive shows safe torque off

Nothing on it, right. The connector is empty, I assumed it was for later when the safety relay goes in. Pretty sure that's on me for not asking sooner...

3 weeks ago
Reply
RE: PID_Compact drives the chiller valve wide open when the tank gets cold, S7-1200

Valve is signal to open, 20 mA fully open, meter matches Output within a tenth. Field's honest. So I think it's the block.

3 weeks ago
Reply
RE: PanelView Plus 6 numeric input writes 12 or 0 when the operator types 12.5, INT tag

Looked at it properly. The logic does Dose_SP divided by 10 into a REAL, so yes, it wants tenths, 125 for 12.5. So the old screen must have been writi...

3 weeks ago
Reply
RE: 1769-L33ER faults type 4 code 20 when the recipe number from the HMI reaches 20

Nowhere, it goes straight in. And 25 on the 25 array faulted, so that's the same thing as 20 on the 20 array. Zero based, I'd read that somewhere and ...

3 weeks ago
Reply
RE: PNP prox on an ET 200SP F-DI safety input, short-circuit to P fault from the first scan

Nothing is broken. Part number of the sensor, the full one? And where does the brown wire go, the panel 24V bus or the VS sensor supply terminal for t...

3 weeks ago
Reply
RE: ET 200SP F-DQ 4x24VDC PM read-back error the moment it switches a contactor coil

Part number of the module, the full 6ES7 one, and list me the wires: A1 to which terminal, A2 to which terminal. Exactly as they are, not as you meant...

3 weeks ago