Ask us for the NATR with the machine next time, we do fit them.
Went relay. 440R-D22R2, both E-stops and the door on the two channels, monitored reset, two 100S-C09 in series with the NC mirrors in the loop, and bo...
Went with an Ewon Cosy on the machine subnet, outbound only, key switch on the panel door wired to its digital input, plant holds the key. Our portal ...
End user pulled the copper out and ran KX extension back to the 1769-IT6, polarity checked with a lighter on the tip. Zone 3 within 1 degree of the ha...
Fair. For a palletiser, compare first.
Next contractor won't even notice. That's the goal.
Changed it. The lock output now waits on a safety task timer started when the STO drops, preset set by the customer's safety engineer comfortably over...
Update level in the handover email from now on. Mine too.
Ended up with the NC task at 500 us, PLC at 1 ms, core isolated. Retuned the applicator axis Kv and the customer signed off the registration. Exceed c...
Array of a UDT in the controller. UDT Recipe with your 22 members plus a STRING for the name, Recipes[50], and Recipe_Active of the same UDT that the ...
Site guy plugged in and set Use router to 192.168.1.250 off my instructions, downloaded it. Ping answers, TIA goes online through the tunnel, support ...
Took the outbound idea to their IT and they liked the direction. Two things back. Who controls when the session is open, they don't want it always on,...
Partly on me. Our wiring drawing says "T/C extension" and nothing about the wire type, so stores picked a colour and I guess nobody questioned it. Dra...
There's your answer, and I've done this to customers myself. A v12 MER will not run on v8 firmware. Runtime files load on equal or newer firmware, nev...
I would just generate a new signature and lock it. If the routines match the archive nothing has changed. Half our machines out in the field have lost...