Put the clock version in on Thursday. GSV WALLCLOCKTIME into a 7 element DINT array, the date written to a retentive tag when the operator presses Fil...
That's the shape I was after. One thing though, this station drops power more often than I'd like, maybe a couple of hours at a time when the co-op ha...
24.8 days. That explains the five days exactly. So I think that's it for a long TON anywhere, it's a ceiling on the instruction rather than something...
That I'll take. Queue on the box, push to the share.
Not the server room. Small fanless box in or beside the panel, one job on it, writing locally. The day IT does something clever with the network at le...
That is the question. If Wednesday had jams and Tuesday didn't then I reckon there's your 300, because your counter has no idea which way the belt is ...
Polling is the wrong shape for events. Latch the reason code and a sequence number into a small event buffer in the controller, say 32 deep, and have ...
That works right up to the first network hiccup, then you've no idea what the machine was doing for ninety seconds and the operator gets a dropdown fo...
Put a timestamp member in while you are in there. When the link to the report drops for an hour you want to know when the number was true, not when it...
192.168.1.x on both ends. Half the remote tickets I get.
Three weeks logged. The 60 percent band sits 1.9 to 2.3. Full speed band 3.2 to 3.6. Set a high alarm per band at 1.5 times that band's average, a ra...
Put a valve on the second zone. Then it's a number too.
All three are standard. Permissive: a key switch or a button wired to the router's digital input, so the plant turns access on and off. Scope: the rou...
RPI to 100 ms yesterday afternoon. Zero drops overnight, first clean night in a month. The scraper permissive is moving to a hardwired pair through th...