Filter's been in a 100 ms periodic task with K = 0.1 since yesterday afternoon. The number's steady to a gpm and it follows a pump start in a second o...
There's your 40 seconds. Open the PID, Configuration tab, look at the timing mode and the update time. I'd bet it's on periodic with .UPD at 0.5 to ma...
What our remote sites and every OEM we work with accept is an outbound VPN router on the machine subnet. The box dials out to a broker, nothing inboun...
It moves, yes. 2.1 at the normal 60 percent speed. 3.4 at full speed when the second zone calls. So the number depends on what the pump's doing at the...
Drop the radio sites to a 10 s scan class, pretty sure nothing on a pump changes faster than that, and the burst shrinks with it. Ours log at 10 s wit...
That's your 8 degrees. Wired as 2 wire the module measures the RTD plus both leads. 80 m of 0.75 is about 2 ohms a core, near 4 ohms for the pair, and...
Are those four links all remote DCOM, historian box to server box? And what's in the historian's Windows event log at 6.10, System and Application? Wh...
Moved the meter cable out of the tray it was sharing with the drive output leads, and the shield was grounded at both ends so that's at the panel bar ...
Meter was 8E1 from the factory and the analyzers 8N1, and the gateway port can only be one of those, so the meter never decoded a request at all. Set ...
Two things the PLC can do. First, count load seconds per hour overnight: a timer on the load solenoid output, totalised per hour, stored. With the pla...
Didn't know there was one separate from the RPI, maybe I've never looked properly. I can't see it on the Connection tab, just RPI 20 ms and the inhibi...
Unit IDs 2, 3, 4. Both analyzers read now and RX is blinking on the gateway. Flow meter still nothing, no exception either, the request just times out...
Pulled the signal pair out of the duct and ran it in its own conduit for the last 20 ft, shield still grounded at the panel only. Flat now, 0.2%, with...
Left at the default, 255 I think. All three SCADA devices point at the gateway's IP, port 502, with different register addresses. I never set a unit I...