Cast to integer in the function node, header row added, three nights clean now. Manager opened it Monday and the weekend was in it. First time. The o...
Automatic reset, download, XV101 drops the moment the fill step exits. Overlap's gone off the trend and the OTUs are out of the dose action. So it wa...
The spare's the same cable type, so you've bought yourself the same problem a few weeks later. Standard EtherCAT cable isn't rated for a cable carrier...
Added the Yesterday tags, that part was ten minutes. Node-RED as a service on the PC, an EtherNet/IP node reads the three tags at 00:30 and writes a l...
Changed the module in the config to the relay version this morning, downloaded, ERROR LED off, packer running. Rewired the output commons the way the ...
Battery in this morning. BAT LED off, OK green, running on the March file. So a flat BA1 from 2016 and an L61 that holds the program in RAM. Forty mi...
A moving cable and a clean cut at slave 14. That's frame loss on one segment, it isn't the cycle time and it isn't firmware. Go and look at where the ...
The exceeds were the machine. The applicator is a tuning question that 250 us was hiding. That cam was tuned at 250 us and it's now following the mast...
Normal on the first cycles, the clocks have to converge before that sync error clears. If it clears in a few seconds and stays clear, leave it alone. ...
PC stays on, nobody's logged in after 17:00. Count resets at midnight, there's a rung that zeroes it on the day change. Nothing keeps yesterday's numb...
Don't scan. I've never opened that tab, so that's my own default rather than a decision. What do the other two options do?
Old one: 6ES7 223-1BL32-0XB0. New one: 6ES7 223-1PL32-0XB0. Both say DI16/DQ16 on the front. Clip's in, checked it with a flashlight. Reseated it aga...
Then start at 1 ms and prove it needs less. At 250 us with 30 slaves you're spending a fair chunk of the cycle just getting the frame on the wire, plu...