design tab shortcut PAL points at 192.168.10.21, backplane, 0, Palletizer. runtime tab same. the old name is still sat in the path, its greyed out in ...
no card. the old cpu has one, it's still in the old cpu in the bin. MAINT is off. display overview says no memory card or similar. same project, yeah.
fitted the 100 c09d01 at 04:00, 522 and 523 on the nc terminals, edm reset first go, ran the rest of the night. edm time left where it was. our safety...
stores has a 100 c09d01 on the shelf two bins over, nc built in, symbol on the side like you said. thats the one?
spare scrolls 192.168.10.41 then a line about duplicate and a mac, cant read it in time. line 2 guy says his palletizer en2t scrolls the same thing, 1...
old 100s has an nc contact built in, terminals 21 22 on the front, wire 522 in and 523 out. new 100 c has nothing there, just coil a1 a2 and the poles...