RE: S7-1200 bit set at the end of OB1 is seen one cycle late at the top, trace shows the lag
There's your cycle. OB1 runs top to bottom, once per cycle. Network 1 reads Part_Present as the previous cycle left it. Network 2 then sets it. The ne...
2 hours ago
Forum
RE: S7-300 stops whenever a PROFIBUS slave drops, OB 86 not loaded
It's not the cable and not the firmware. The buffer already told you: OB86 isn't in the CPU. Which STEP 7 version, and have you got the project? Look ...
7 hours ago
Forum
RE: S7-300 SM 331 level scaling shows only 0, 25, 50, 75 percent, DINT maths
Yes. VAT is the variable table. ITD gives you a DINT, DIV_DI on two DINTs gives you a DINT, so 10018 / 6912 is 1 and the .449 is gone before you ever ...