RE: S7-300 stops whenever a PROFIBUS slave drops, OB 86 not loaded

A 2A supply with a panel heater on it. Look there first.

3 weeks ago
Reply
RE: PROFIBUS DP at 1.5 Mbit/s over a 300 m segment, far slaves drop with BF flashing

Dropped it to 500 kbit removed link HW Config, DP master system properties, Network Settings, transmission rate 500 kbit/s, downloaded. Every slave c...

3 weeks ago
Reply
RE: S7-300 goes to STOP with SF, diagnostics buffer says OB 121 not loaded

OB121 is the programming error OB. Cycle time is OB80. Different things. Without OB121 a 300 stops on every programming error. That is why it stops. ...

3 weeks ago
Reply
RE: Upload from S7-300 has no symbols or comments, only absolute addresses

There is no upload with symbols on a 300. Symbols, comments and network titles live only in the offline project, the CPU stores compiled code and noth...

3 weeks ago
Reply
RE: CompactLogix solenoid output chatters, rung is true in one place and false in another

Yes. Same thing on STEP 7 with two assignments to one Q address, the cross reference list shows both and the last one in the cycle wins. On a 300 you'...

3 weeks ago
Reply
RE: PROFIBUS DP at 1.5 Mbit/s over a 300 m segment, far slaves drop with BF flashing

Same drum, same part number, I checked the print on the jacket. Old run and new run are both 6XV1830-0EH10, so it isn't the cable type. Baud rate is s...

3 weeks ago
Reply
RE: S7-1200 bit set at the end of OB1 is seen one cycle late at the top, trace shows the lag

There's your cycle. OB1 runs top to bottom, once per cycle. Network 1 reads Part_Present as the previous cycle left it. Network 2 then sets it. The ne...

3 weeks ago
Reply
RE: S7-300 stops whenever a PROFIBUS slave drops, OB 86 not loaded

It's not the cable and not the firmware. The buffer already told you: OB86 isn't in the CPU. Which STEP 7 version, and have you got the project? Look ...

3 weeks ago
Reply
RE: S7-300 SM 331 level scaling shows only 0, 25, 50, 75 percent, DINT maths

Yes. VAT is the variable table. ITD gives you a DINT, DIV_DI on two DINTs gives you a DINT, so 10018 / 6912 is 1 and the .449 is gone before you ever ...

3 weeks ago