No reboot, not on a 1756-L72 for this. The message says program, not routine. Look at every routine in that program in the organizer. Any of the icons...
Stores needs the mirror contact called out on the bin label, so nobody hands out a plain 100-C again.
That's the one. 522 and 523 on its NC, tape off.
We had exactly that on a line rebuild last year. It's a property on the server itself, not a Windows service. In the Administration Console, right cli...
One photo, one question. What's on the front of the old 100S in your photo that isn't on the front of the new 100-C? And what wire number lands there.
Set it to 9, downloaded, still faulted. Went online with the adapter, Module Info tab, pressed Set Chassis Size, power cycled the rack. All eight modu...
Chassis Size says 8. Eight modules, eight. I didn't touch it, it already matched.