RE: Studio 5000 refuses online edit, pending edits exist in another routine

No reboot, not on a 1756-L72 for this. The message says program, not routine. Look at every routine in that program in the organizer. Any of the icons...

1 hour ago
Reply
RE: Compact GuardLogix EDM feedback fault after a 100-C replaced the 100S contactor

Stores needs the mirror contact called out on the bin label, so nobody hands out a plain 100-C again.

4 hours ago
Reply
10 hours ago
Reply
RE: FactoryTalk View SE 13 alarm and event server dead after every server reboot

We had exactly that on a line rebuild last year. It's a property on the server itself, not a Windows service. In the Administration Console, right cli...

12 hours ago
Reply
RE: Compact GuardLogix EDM feedback fault after a 100-C replaced the 100S contactor

One photo, one question. What's on the front of the old 100S in your photo that isn't on the front of the new 100-C? And what wire number lands there.

3 days ago
Reply
RE: 1734-AENT faults every module in the rack after adding a 1734-IB8 on the end

Set it to 9, downloaded, still faulted. Went online with the adapter, Module Info tab, pressed Set Chassis Size, power cycled the rack. All eight modu...

4 days ago
Reply
RE: 1734-AENT faults every module in the rack after adding a 1734-IB8 on the end

Chassis Size says 8. Eight modules, eight. I didn't touch it, it already matched.

1 week ago