RE: Ultrasonic level in a wet well jumps 2m and short cycles the lead pump

Four good years then three bad weeks means something changed, not something wore out. Where exactly is it mounted, and how far is the face off the hi...

3 weeks ago
Reply
RE: Studio 5000 refuses online edit, pending edits exist in another routine

Upload it tonight, not tomorrow. That's how the next thread starts.

3 weeks ago
Reply
Reply
RE: Panel shop used a standard red 22mm pushbutton as the E-stop, auditor flagged it

you've got it. Second block on a fingertip button is two of the wrong thing.

3 weeks ago
Reply
RE: 1756-EN2T webpage media counters, what do FCS errors mean when a rack shows 16#0204

That plug is your problem. A short strand in a hand crimp is a bad contact that works until it doesn't. The sealer rack is the only one showing it bec...

3 weeks ago
Reply
RE: PNOZ X3 safety relay drops out for a second every time the 30kW mixer drive starts

Look at your drawing. I'll bet it shows two supplies, control and safety, and somebody landed everything on the first one because the second never got...

3 weeks ago
Reply
RE: MSR127RP won't reset after replacing a contactor, K1 K2 LEDs stay off

Then the drawing is right and the panel is wrong. That's your open loop.

3 weeks ago
Reply
RE: 1756-EN2T faulted, 16#0204 connection request error after weekend power outage

999 means take the address from a BOOTP or DHCP server. Whoever built it in 2019 gave it .20 with the BOOTP-DHCP tool and, if I remember right, that t...

3 weeks ago
Reply
RE: 1756-EN2T webpage media counters, what do FCS errors mean when a rack shows 16#0204

Post a photo of the EN2T's own patch cable, the plugs, both ends. Was it made on site? The counters on that page are for the EN2T's port only, the lin...

3 weeks ago
Reply
RE: Panel shop used a standard red 22mm pushbutton as the E-stop, auditor flagged it

One question off your photo. When you hit that button, does it latch and stay in until you twist it out, or does it spring back the moment you let go?

3 weeks ago
Reply
RE: MSR127RP won't reset after replacing a contactor, K1 K2 LEDs stay off

One question. What's the wire number on S33, and where does the drawing say it goes before it gets to the button? Follow it on paper, not in the panel...

3 weeks ago
Reply
RE: Studio 5000 refuses online edit, pending edits exist in another routine

No reboot, not on a 1756-L72 for this. The message says program, not routine. Look at every routine in that program in the organizer. Any of the icons...

3 weeks ago
Reply
RE: Compact GuardLogix EDM feedback fault after a 100-C replaced the 100S contactor

Stores needs the mirror contact called out on the bin label, so nobody hands out a plain 100-C again.

3 weeks ago
Reply
3 weeks ago
Reply
RE: FactoryTalk View SE 13 alarm and event server dead after every server reboot

We had exactly that on a line rebuild last year. It's a property on the server itself, not a Windows service. In the Administration Console, right cli...

3 weeks ago