Nobody ever admits to hardening a server. Glad it was free.
Kepware is TCP, class 3, it doesn't care. Your I/O is multicast. Two things: is there an IGMP querier on that VLAN, and what's the snooping group time...
Design (local) tab has the shortcut CP1 pointing at the L33ER. Runtime (target) tab is empty, no shortcut in it at all. Does that matter? Test Applica...
Compatible Module did it. Module Properties, Change, keying dropdown, downloaded on the lunch break, drive went green and the belt ran on the first st...
Two billion Wh, 24 days at 3.5 MW. The maths checks out.
Terminal says 11.00 and the MER was built as V11, so that matches. Tags on the PLC are all DINT and REAL, nothing odd about them, same tags the old te...
Before you touch the licence: services.msc on that server. Look for the FactoryTalk Activation helper service, the exact name has a version suffix on ...
Old one was a 4 point something, new one shows 7.001 on the keypad. Decel is 5 seconds, load is a short belt, not much on it. So the new drive is newe...
Run the FactoryTalk Directory Configuration Wizard on the client. Local or Network?
Is Wh_Total a DINT or a REAL, and what was the last value the historian logged before it went negative? The exact digits, not the kWh on the screen.