Forum

mira88
@mira88
New Member
Joined: Sep 15, 2025
Last seen: Sep 19, 2026
Topics: 4 / Replies: 19
Reply
RE: S7-1500 OPC UA connection refused from the office subnet, works from the plant

Same trap here, a 102 rule from an old ticket nobody had questioned.

3 weeks ago
Reply
RE: Ignition to KEPServerEX OPC UA, BadCertificateHostNameInvalid from the server room only

A blank DNS suffix. Wouldn't have guessed that from the fault message.

3 weeks ago
Reply
RE: Ignition Edge MQTT Transmission, ten minute gaps in cloud data after every WAN drop

The longer holes are probably the reconnect backoff, ours does the same thing.

3 weeks ago
Reply
RE: Publish MQTT straight from the S7-1500 with LMQTT, or put an edge gateway in?

Gateway it is. What decided it was the cycle time. 9 ms on a bench CPU with nothing else in it, and on a real line with a 2 ms OB30 that's a stopped m...

3 weeks ago
Reply
RE: Ignition MQTT Engine shows no tags, broker sees every message from the gateway

Gateway has a Sparkplug B option. One metric first, then the lot. Tags turned up under Edge Nodes with the group and node ID as I'd set them, and pull...

3 weeks ago
Reply
RE: Remote view of a PanelView Plus 7 line HMI from home, IT refuses any port forward

Outbound is the shape of the answer, and nothing inbound. A small VPN router on the machine network that dials out on 443 to a hosted service, eWON Co...

3 weeks ago
Reply
RE: Ignition Edge MQTT Transmission, ten minute gaps in cloud data after every WAN drop

QoS only covers a message the client has already handed to the broker. If the client's disconnected nothing is queued unless the client queues it, and...

3 weeks ago
Reply
RE: Publish MQTT straight from the S7-1500 with LMQTT, or put an edge gateway in?

Went and looked. Cycle time jumps from 4 ms to about 9 ms in bursts while it's reconnecting, every few seconds, for as long as the broker is down. And...

3 weeks ago
Reply
RE: Ignition MQTT Engine shows no tags, broker sees every message from the gateway

Added a Custom Namespace, plant/# with JSON on. Folders appeared, plant, line2, temp, with value and ts as tags. Values update, so that works. Qualit...

3 weeks ago
Reply
RE: OEM wants TeamViewer on the FactoryTalk View SE PC for remote support, IT says no

Start from what leaves the plant, not what comes in. Their IT said no to a desktop sharing tool because it's a full session on a Windows box on the li...

3 weeks ago
Reply
RE: Ignition to KEPServerEX OPC UA, BadCertificateHostNameInvalid from the server room only

Could be the certificate rather than anything on the network. On the KEP box open the OPC UA Configuration Manager, Instance Certificates, select the ...

3 weeks ago
Reply
RE: S7-1500 OPC UA connection refused from the office subnet, works from the plant

What does the CPU's certificate list say about the office client, trusted or rejected? An untrusted cert gets bounced fast too, might be that. And is ...

3 weeks ago
Reply
RE: S7-1500 OPC UA server connects, UaExpert shows no DB variables

Ticked. DB_Line had the accessible attribute off on the block itself, someone had unticked it when they tightened the HMI down, and every tag undernea...

3 weeks ago
Page 1 / 2