Correct. STO is hardwired on the 5500, it doesn't care that there's no safety project. Two inputs, if both aren't at 24V the drive won't enable and MS...
Ran a week of production. The gantry stays inside a few hundredths over the full 2 m and the Y2 following error is flat. That restart sync error clear...
Not more gain. With feedforward at 0 the position loop only pushes when there's already error. At speed it trails the command by whatever error it tak...
Then 1600 x 0.34 is 544, plus 128 for the 30 mm, about 670 mm before anyone argues. Move the curtain, or cut the stop time hard and recalculate. Faste...
Not an axis parameter. Display says STO, so the drive's safe torque off inputs aren't seeing 24V. What's wired to the STO connector on the front, the ...
What's the jog velocity, and is there a hold time set on that button? Some people set a hold time of a few seconds so the press registers, and that'd ...
Two ways to do this properly, and neither one is a timer off Stop. Standstill from a safe speed monitor: encoder or a safety rated speed input into t...
Post the trend. And Axis Properties, Position Loop tab, what are the gains and what's Velocity Feedforward set to? Also gearbox ratio and whether tuni...
Both drives to DC-Synchron, activated. First slave is an EK1100 then EL1008s, the drives are boxes 6 and 7. Long move now, the ramp's gone, Y2 error i...
While you wait for a meter, the arithmetic. ISO 13855: S = K x T + C. For a curtain up to 40 mm resolution you start with K 2000 mm/s, and if that com...
What does the motion actually need? On Kinetix I run most packaging axes at 2 ms coarse update and nobody can tell. What's the fastest thing on that l...
DC tab on both AX8000 says SM-Synchron. Never looked in there, I took whatever the scan gave me. Y1 and Y2 are both on the same setting though, so I'm...
Trend it before anything else. Spindle speed from Stop to zero, heaviest wheel, no load, worn belt if it has one. And to be clear, right now the lock ...