Nobody ever knows why it was 60%.
Laminated card in the panel door. Best place for it.
Product probably had a value at home. Bounded loop, either way.
Ran Compare against the commissioning ACD, still on V33. Safety task identical, only the standard timer preset differs. Generated a new signature, loc...
Went with the running sum. Add new, subtract oldest, divide once, and the array is now a ring buffer with an index. T_Weigh max scan time is 4.6ms wit...
IT had deleted and recreated the account rather than resetting it, so the SQL login existed with no user in the database. DBA mapped it back with data...
1 place on the display too. Both objects have to agree.
Right. A rung with no conditions runs every scan, so every 10ms or so that MOV puts 50 straight back. The panel wins for one scan and then loses. Two...
Wrote 047E for a second at startup and then 047F on the run command. Drive went to operation enabled, motor turned, speed followed the setpoint. Ran i...
> Isn't the error negative then? Pretty sure it is, but the PIDE's CV was allowed to climb to 100% while the valve only ever saw 60%. It has 40% t...
Set it to Automatic reset. On the last scan of a step that's going inactive, Logix runs the action once more as a postscan, OTEs go off and timers res...
Password had expired Friday 18:40, IT confirmed it. Reset it, updated the connector, started the configuration. Login errors stopped. Cache file isn'...
> Max Scan Time 23.4ms with the routine in, 4.1ms without. Continuous task max is 38ms. So yes, it blows straight past 20. finn, yes, and if the p...
> Was the safety task locked when the contractor went online, or only signed? Signed, but I now think not locked. Our commissioning notes say lock...