> .PRE is holding a negative number DINT. Signed 32 bit, tops out at 2147483647, and your preset is in milliseconds, so the ceiling on any TON is ...
Went with the box in the end. Small industrial PC in the MCC room, Kepware moved onto it with the config exported into our git repo, a scheduled task ...
Network is fine to be fair, it's a flat plant network and the packing lines sit on the same switch stack as the office. What worries me more is that n...
That was the whole of it. The module I pulled off the filler on Friday went back in the crib, and the night fitter took it straight back out the same ...
Same trap in Logix. A download is a fresh data table.
Nothing wrong with a boring answer that stays running.
Mirrored the port and sat through the 06:00 clean with Wireshark running. No storm. The link is quiet right up to the second the modules go, so that o...
> the link letting go quietly It does that. I've had Classic drop a topic after a Windows update restarted the service and the cells keep the last...
> does the PLC write the file itself Depends entirely on what the PLC is, and you haven't said. A 1769 CompactLogix can't write a CSV anywhere you...
That's it. Four drives read Fault on C143 and the capper read Hold Last. Set it back to Fault off the keypad, pulled the patch lead with the line empt...
RPI is 20ms on all five, multiplier untouched, so we're talking 80ms before it gives up. Two minutes is not that. And the other four faulted off the ...
Unmanaged 8 port thing that came with the machine, no diagnostics on it to speak of. It's been replaced with a Stratix 2000 now. Drive fault queue is...
Stratix 5700, the eight port one, uplinked to the core in the MCC room. One VLAN for the lot of it. I went back over the times against the shift log ...