RE: Daily production count from a CompactLogix 5069 into Excel, no SCADA on site

Good result. The clock change one is worth ten minutes in October.

3 weeks ago
Reply
RE: PowerFlex 525 F059 Safety Open on a machine with no safety circuit

Better it shouts than sits there quiet. Glad it was a 20 cent jumper.

3 weeks ago
Reply
3 weeks ago
Reply
RE: Ignition can't reach a 1756-L72 on VLAN 20 from VLAN 10, IT says routing is fine

Glad it wasn't the driver. Write 10.20.1.1 on the panel door.

3 weeks ago
Reply
RE: Node-RED OPC UA client to S7-1500 fails with BadSecurityChecksFailed, None policy works

That was it. The node had a fresh certificate in its own folder, I think from the module update that week, and the .der I exported was the old one. Po...

3 weeks ago
Reply
RE: Daily production count from a CompactLogix 5069 into Excel, no SCADA on site

Then the first fix is in the PLC, not the PC. Before the rung zeroes the count, move it into Yesterday_Good and Yesterday_Reject DINTs with the date a...

3 weeks ago
Reply
RE: MSG read works for one tag and errors for another on the same target controller

Set External Access to Read Only on the packer tag, online edit, accepted. MSG went .DN on the next trigger, 500ms, rejects showing on the line overvi...

3 weeks ago
Reply
RE: Ignition MQTT Engine shows no tags, broker sees every message from the gateway

That's why Sparkplug exists. A custom namespace has no death certificate, so the last value just sits there. If the gateway can publish Sparkplug, do...

3 weeks ago
Reply
RE: CompactLogix periodic task overlap count climbing, PanelView sluggish

Set T_Fast to 10ms. Overlap count stayed at 0 through a full shift at rate, max scan 6.9ms. PanelView buttons respond straight away. Flight tracking i...

3 weeks ago
Reply
RE: PowerFlex 525 F059 Safety Open on a machine with no safety circuit

F059 isn't a parameter thing, so stop loading files at it. It's the safety terminals, nothing else. Look at the control terminal block on the new driv...

3 weeks ago
Reply
RE: Ignition can't reach a 1756-L72 on VLAN 20 from VLAN 10, IT says routing is fine

Then .254 doesn't exist on VLAN 20. Ask IT for the actual SVI address on VLAN 20, not what their standard says it should be. Ping .254 from your VLAN ...

3 weeks ago
Reply
RE: Node-RED OPC UA client to S7-1500 fails with BadSecurityChecksFailed, None policy works

Auto accept ticked as a test, downloaded, connected first time with Sign and Encrypt. Reads fine. Then I unticked it, imported the .der, added it to ...

3 weeks ago
Reply
RE: Logix EQU on two REALs never goes true, 0.1 + 0.2 against a 0.3 setpoint

Smallest test first. Make the watch window show more digits, set the tag style to Float and widen the column, or put Sum into a tag with 9 decimals. W...

3 weeks ago
Reply
RE: 1756-EN2T off the network after IT enabled port security, switch port err-disabled

Not a faulty NIC, a NIC doesn't send a bad MAC, it sends its MAC. Ask IT for show port-security interface on that port. It lists the allowed MAC and t...

3 weeks ago
Reply
RE: MSG read works for one tag and errors for another on the same target controller

Both 33.011. Tag editor on the packer: CP_Count_Reject, DINT, controller scope, External Access says None. CP_Count_Good next to it says Read removed ...

3 weeks ago