It isn't the rate, it's the width. The input image gets read once per scan. Your scan is 12 to 20ms and the pulse is 5ms, so any pulse that starts and...
About 8 m, from the last EK1100 in the main panel to the coupler in the gripper panel. Standard EtherCAT cable, the green stuff, and it runs through t...
> Last two numbers of your path 1,0. Backplane, slot 0. But the controller in B is in slot 3, I said that myself. So 1,3, I think. Is that really ...
Which part do the electricians open when the skid stops? The sequence itself, or the reason a valve won't open?
What happens when Product isn't in the array? Read the loop again with that case in mind, and tell me what the IF at the bottom is for. Also, continuo...
Fitted a second 24VDC 5A supply for the PLC and the rack. Valves and HMI stay on the 10A. Commons tied at the ground bar. Jogged the manifold 20 times...
Two things stacked. T_Fast running up to 6.8ms in a 5ms period runs past the next trigger whenever a scan goes long, overlap, and it takes priority ev...
What are the drives running in, DC-Synchron or SM-Synchron? Each AX8000 has a DC tab in TwinCAT. A ramp that grows with the move and resets when it st...
Not the port. Overlap count going up means the 5ms trigger is arriving before the previous pass of T_Fast is done. What's the task's watchdog, what pr...
The coils say 24VDC 0.21A. So 8.4A if all 40 fire at once, plus the PLC and the rack and the HMI. That's over 10 isn't it.
One supply, 24VDC 10A, feeds the PLC, the rack, the valve manifold and the HMI. That's everything on it I think, panel builder's label. Meter can't ca...